Additions to Table A1-10

(Appendix 1)

(2)

Availability

(4)

Parameter

Number

Monitor Item

Description

Display

Unit

Analog Monitor

Output Level

0 1 2 3

Modbus

Address

U1-50

Feedback

Monitor

Feedback Level

0.01 V

10V / 10V

feedback signal

A A

A

A

00D0H

U1-51 PID

Error

Difference between setpoint and
feedback

0.01%

10V / max. output

freq. (E1-04)

A A

A

A

00D1H

U1-52 PID

Output

Output of the PID control algorithm
before its added into the main
frequency reference

0.01%

10V / max. output

freq. (E1-04)

A A

A

A

00D2H

U1-53

Proportional

Value

Output value of just the proportional
portion of the PID algorithm

0.01%

10V / max. output

freq. (E1-04)

A A

A

A

00D3H

U1-54

Integral

Value

Output value of just the integral
portion of the PID algorithm

0.01%

10V / max. output

freq. (E1-04)

A A

A

A

00D4H

U1-55

Derivative

Value

Output value of just the derivative
portion of the PID algorithm

0.01%

10V / max. output

freq. (E1-04)

A A

A

A

00D5H

U1-56 PID

Setpoint

Actual PID setpoint
(Analog value + b5-07)

0.01V

10V / 10V

setpoint

A A

A

A

00D6H


NOTE: The standard software PID monitors (U1-24: PID Feedback, U1-36: PID Input, U1-37: PID Output, and U1-38: PID
Setpoint) are not used in this software. Please use monitors U1-50 through U1-56.

Addition to Table 5-2 Multi-Function Input Terminal Data Settings

(Section 5.32)

(2)

Parameters H1-01 thru H1-06 and terminals 3 thru 8.

Availability

(4)

Data Function

Description

0 1 2 3

30

PID Integral

Reset

Closed = Reset integrator to zero
See Paragraph 5.36F

B B B

B

80 Integral

Hold

Closed = Hold integrator at its present level
See Paragraph 5.36F

B B B

B

81

Positive

Integral Hold

Closed = Will allow integrator level to decrease, but not
increase. See Paragraph 5.36F

B B B

B

82

Negative

Integral Hold

Closed = Will allow integrator level to increase, but not
decrease. See Paragraph 5.36F

B B B

B

Addition to Table 5-3 Multi-Function Output Terminal Data Settings

(Section 5.33)

(2)

Parameters H2-01 thru H2-03 and terminals 9, 10, 25, 26 & 27. Plus DO-02C option card F5-01 & F5-02.

Availability

(4)

Data Condition

Signal

Level

0 1 2 3

40 High

Position

Closed When PID Feedback is above High position b5-10

B B B B

41 Low

Position

Closed When PID Feedback is below Low position b5-11

B B B B


Addition to Section 5.30 Multi-Function Analog Input Terminal Data Settings

(2)

Parameters H3-05 & H3-09 and terminals 16 & 14.

Availability

(4)

Data Function

Description

0 1 2 3

20

PID Setpoint

Provides a setpoint signal for use with PID control.

B B B

B

21

PID Feed-

back Analog

Input Bias

Mathematically adds to the feedback signal when using PID
control.

B B B

B

(2)

GPD515/G5 Technical Manual TM4515

(4)

Capability to view and set specific parameters is dependent upon the Access Level (A1-01) and Control Method (A1-

02: 0 = V/f, 1 = V/f w/PG, 2 = Open Loop Vector, 3 = Flux Vector) the drive is programmed for. Each column represents
the minimum Access Level for a given Control Method: 0 = Operation only; Q = Quick-start; B = Basic; A = Advanced; - =
not available.

Advertising