Yaskawa Electric America, Inc –

www.yaskawa.com

IG.AFD.25, Page 5 of 6

Date: 10/7/09, Rev: 09-10

‰

Finish the Modbus TCP/IP Option Card installation.
„

Remove power from the drive and wait for the charge lamp to be completely
extinguished. Wait at least five additional minutes for the drive to be
completely discharged. Measure the DC bus voltage and verify that it is at a
safe level.

„

Reinstall all drive covers and the operator keypad. Apply power to the drive.

„

Set parameters b1-01 and b1-02 to their appropriate values. Refer to the table
to the right for available b1-01 and b1-02 values.

„

Refer to the appropriate programming or parameter access manual for a
complete list of drive parameters and registers available. A list of applicable
manuals is available at the end of this document.

Parameter Function

Data

Description

Default

0 Digital

Operator

1 Terminal

Strip

2

Built-in Modbus RTU

3

Option Card (Modbus TCP/IP Option
Kit)

b1-01

Frequency

Reference

Source

Selection

4

Pulse Input (F7 and G7 Only)

1

0 Digital

Operator

1 Terminal

Strip

2

Built-in Modbus RTU

b1-02

Run

Command

Source

Selection

3

Option Card (Modbus TCP/IP Option
Kit)

1


‰

Important Modbus TCP/IP notes.
„

It is strongly recommended that shielded CAT-5 cable be used for all network cables.

„

A maximum of 10 simultaneous connections are allowed.

„

The run command and frequency reference may only be accessed through UNIT ID 1. While the drive is in remote run mode, the run command must be continually
refreshed within the configured EF0 timeout value. If the run command is not refreshed within the set timeout period, an EF0 fault will occur. Refer to the appropriate
drive manual for information on EF0 and setting the appropriate drive response. If a UNIT ID 1 connection is active, the NS/CON LED will blink at approximately a
500ms cycle.

„

The TCP/IP connection must be refreshed within 60 seconds. If it is not refreshed within 60 seconds, the connection will be closed.

„

This implementation of Modbus TCP/IP supports Modbus functions 3 (read multiple registers), 6 (write single register), 16 (write multiple registers), and 23
(read/write multiple registers).

„

Refer to the appropriate programming or parameter access manual (TM.XX.11) for a complete list of drive parameters and registers available. A list of applicable
manuals is available at the end of this document. Aside from command registers, Modbus TCP/IP and Modbus RTU share all other registers.

„

The table below lists the Modbus TCP/IP command registers. These are different from Modbus RTU command registers. These are designed to be used as part of the
standard PLC I/O or scan table, where fast response is required. Other register values should be accessed via individual messages, i.e. via an MSTR block.

„

Addresses 0001h, 0002h, 0003h, 0004h, 0007h, 0008h, and 0009h may be written while all other registers in the table below are read only. Addresses 0001h and 0002h
may only be accessed through UNIT ID 1 (see above).

Address

Description

Address

Description

Address

Description

0h Forward

Run

Input

Ah @ Remote Mode

4h EF7

External Fault 7

1h Reverse

Run

Input

Bh Multi-Function Output 1 (M1-M2)

5h

Reserved

2h Multi-Function Digital Input S3

Ch Multi-Function Output 2 (M3-M4)

6h

Reserved

3h Multi-Function Digital Input S4

Dh Multi-Function Output 3 (M5-M6)

7h

OS

Overspeed

4h Multi-Function Digital Input S5

Eh @ Motor 2 Selected

8h

DEV

Speed

Deviation

5h Multi-Function Digital Input S6

2000h

Status Word 1
(continued)

Fh @ Zero Servo Complete

9h

PGO

Encoder

(PG)

Loss

6h Multi-Function Digital Input S7

2001h

Speed Feedback Monitor (U1-05)

Ah

PF

Input

Phase

Loss

7h Multi-Function Digital Input S8 (G5/F7/G7)

2002h

Torque Reference Monitor (U1-09)

Bh

LF

Output

Phase

Loss

8h External Fault (EF0) Input

2003h

Encoder (PG) Count Channel 1 Monitor

Ch OH3 Motor Overheat 1

9h Fault

Reset

Input

2004h

Frequency Reference Monitor (U1-01)

Dh

OPR

Operator

Disconnected

Ah Multi-Function Digital Input S9 (G7)

2005h

Output Frequency Monitor (U1-02)

Eh ERR EEPROM Write Failure

Bh Multi-Function Digital Input S10 (G7)

2006h

Output Current Monitor(U1-03)

200Ah

Error Signal 2
(continued)

Fh OH4 Motor Overheat 2

Ch Multi-Function Digital Input S11 (G7)

2007h

Analog Input A2 Monitor (U1-16) (Terminal 14 for G5)

0h

CE

Communication

Loss

Dh Multi-Function Digital Input S12 (G7)

2008h

DC Bus Voltage Monitor (U1-07)

1h BUS Option Card Error

Eh Fault Log Trace Clear Input

0h PUF DC Bus Fuse Failure

2h

Reserved

0001h Command

Fh External Base Block Input

1h UV1 Main Circuit Undervoltage

3h

Reserved

0002h Frequency

Reference

2h UV2 Control Power Undervoltage

4h CF

Loss of Control

0003h Torque

Reference/Torque

Limit

3h UV3 Pre-Charge Contactor Failure

5h SVE Zero Servo Error

0004h Torque

Compensation

4h

Reserved

6h EF0

Option Card External Fault

0007h Analog Output FM (21 for G5)

5h

GF

Ground

Fault

7h FBL PID Feedback Loss

0008h Analog Output AM (23 for G5)

6h

OC

Overcurrent

8h

UL3

Undertorque

Detection

1

0h Multi-function Digital Output 1

7h

OV

Overvoltage

9h

UL4

Undertorque

Detection

2

1h Multi-function Digital Output 2

8h

OH

Drive

Overheat

Ah OL7 High Slip Brake Overload

2h Multi-function Digital Output 3 (G5/F7/G7)

9h OH1 Motor Overheat Alarm

Bh

Reserved

3h Multi-function Digital Output 4 (G5/F7/G7) Ah

OL1

Motor

Overload

Ch

Reserved

0009h

Multi-
function
Digital
Outputs

4h Multi-function Digital Output 5 (G5/F7/G7) Bh

OL2

Drive

Overload

Dh

Reserved

0h @

Run

Ch

OL3

Overtorque

Detection

1

Eh

Reserved

1h @ Zero Speed

Dh

OL4

Overtorque

Detection

2

200Bh Error Signal 3

Fh CPF Control Bd Hardware Fault

2h @ Reverse Direction

Eh RR

Braking Transistor Failure

200Ch Analog Input A1 Monitor (U1-15) (Terminal 13 for G5)

3h @ Fault Reset Active

2009h

Error Signal 1

Fh RH

Braking Resistor Overheat

200Dh Digital Input Status (Bit Field of Terminals S1-S8)

4h @ Speed Agree

0h EF3

External Fault 3

200Eh Analog Input A3 Monitor (U1-17) (Terminal 16 for G5)

5h @ Drive Ready

1h EF4

External Fault 4

200Fh PG Count Channel 2 Monitor (when PG-W2 is installed)

6h @ Minor Fault (Alarm)

2h EF5

External Fault 5

2010h Drive Software Number (U1-14)

7h @

Fault

200Ah

Error Signal 2

3h EF6

External Fault 6

8h @ OPE Fault (Keypad Setting Error)

2000h

Status
Word 1

9h @ Power Loss Ride Thru

Advertising