Yaskawa Electric America, Inc. –

www.yaskawa.com

IG.G5HHP.25 Page 5 of 9

Date: 10/12/09 Rev: 09-10

‰

Finish the CM090 Modbus TCP/IP Option card installation.
„

Remove power from the drive and wait for the charge lamp to be
completely extinguished. Wait at least five additional minutes for the
drive to be completely discharged. Measure the DC bus voltage and
verify that it is at a safe level.

„

Reinstall all drive covers and the operator keypad. Apply power to the
drive.

„

Set parameters b1-01 and b1-02 to their appropriate values. Refer to the
table to the right for available b1-01 and b1-02 values.

„

Refer to the appropriate programming or parameter access manual for a
complete list of drive parameters and registers available. A list of
applicable manuals is available at the end of this document.

Param

Function

Data

Description

Default

0 Digital

Operator

1 Terminals

2

Serial Communication Built-in Modbus RTU
Terminals

b1-01

Reference

Source

Select

3

Option Card (CM090 Modbus TCP/IP Option)

1

0 Digital

Operator

1 Terminals

2

Serial Communication Built-in Modbus RTU
Terminals

b1-02

Run

Command

Source

Select

3

Option Card (CM090 Modbus TCP/IP Option)

1

‰

Important Modbus TCP/IP notes.
„

It is strongly recommended that shielded CAT-5 cable or crossover cable be used for all network cables.

„

A maximum of 10 simultaneous connections are allowed.

„

The run command and frequency reference may only be accessed through UNIT ID 1. While the drive is in remote run mode, the run command must be continually
refreshed within the configured EF0 timeout value. If the run command is not refreshed within the set timeout period, an EF0 fault will occur. Refer to the appropriate
drive manual for information on EF0 and setting the appropriate drive response. If a UNIT ID 1 connection is active, the NS/CON LED will blink at approximately a
500ms cycle.

„

The CM090 Modbus TCP/IP Option connection must be refreshed within 60 seconds. If it is not refreshed within 60 seconds, the connection will be closed.

„

This implementation of CM090 Modbus TCP/IP Option supports Modbus functions 3 (read multiple registers), 6 (write single register), 16 (write multiple registers) and
23 (read/write multiple registers).

„

The table below lists the Modbus TCP/IP Command registers. These are designed to be used as part of the standard PLC I/O or scan table, where fast response is
required. Other register values should be accessed via individual messages, i.e. via an MSTR block.

„

Addresses 0001h, 0002h, 0003h, 0004h, 0007h, 0008h, and 0009h may be written while all other registers in the table below are read only. Addresses 0001h and 0002h
may only be accessed through UNIT ID 1 (see above).

Addr

Description

Addr

Description

Addr

Description

0h Forward Run Input

2000h

Status Word

Ah @ Remote Mode

4h EF7

External Fault 7

1h Reverse

Run

Input

Bh Multi-Function Output 1

5h Reserved

2h Multi-Function Digital Input 11

Ch Multi-Function Output 2

6h Reserved

3h Multi-Function Digital Input 12

Dh Multi-Function Output 3

7h OS

Overspeed

4h Multi-Function Digital Input 13

Eh @ Motor 2 Selected

8h DEV

Speed Deviation

5h Multi-Function Digital Input 14

Fh @ Zero Servo Complete

9h PGO

Encoder (PG) Disconnect

6h Multi-Function Digital Input 15

2001h

Speed Feedback (U1-05)

Ah PF

Input Phase Loss

7h Multi-Function Digital Input 16

2002h

Torque Reference (U1-09)

Bh LF

Output Phase Loss

8h External Fault (EF0) Input

2003h

Encoder (PG) Count Channel 1

Ch OH3

Motor Overheat 1

9h Fault Reset Input

2004h

Frequency Reference (U1-01)

Dh OPR

Operator Disconnect

Ah Reserved

2005h

Output Frequency (U1-02)

Eh ERR

EEPROM Write Error

Bh Reserved

2006h

Output Current (U1-03)

200Ah Error Signal 2

Fh OH4

Motor Overheat 2

Ch Reserved

2007h

Terminal 39 Input Voltage (U1-16)

0h CE

Communication Error

Dh Reserved

2008h

DC Bus Voltage (U1-07)

1h BUS

Option Card Error

Eh Fault Log Trace Clear Input

0h PUF

Main Circuit (DC Bus Fuse)

2h Reserved

0001h Command

Fh External Base Block Input

1h UV1

Main Circuit Undervoltage

3h Reserved

0002h Frequency Reference

2h UV2

Control Power Undervoltage

4h CF

Loss of Control

0003h Torque

Reference/Torque

Limit

3h UV3 Pre-charge Failure

5h SVE

Zero Servo Error

0004h Torque Compensation

4h Reserved

6h EF0

Option External Error

0007h Analog

Output

45

5h GF

Ground

Fault

7h FBL

PID

Feedback

Loss

0008h Analog

Output

48

6h OC

Overcurrent

8h UL3

Undertorque

Detect

1

0h Multi-function Output 53-57

7h OV

Overvoltage 9h

UL4

Undertorque

Detect

2

1h Multi-function Output 19-50

8h OH

Drive Overheat

Ah Reserved

0009h

Multi-
function
Digital
Outputs

2h Multi-function Output 20-50

9h OH1

Motor Overheat Alarm

Bh Reserved

0h @ Run

Ah OL1

Motor Overload

Ch Reserved

1h @ Zero Speed

Bh OL2

Drive Overload

Dh Reserved

2h @ Reverse Direction

Ch OL3

Overtorque 1

Eh Reserved

3h @ Reset

Dh OL4

Overtorque 2

200Bh Error Signal 3

Fh CPF

Hardware

Fault

4h @ Speed Agree

Eh RR

Braking Transistor

200Ch Analog Input 42 Value (U1-17)

5h @ Drive Ready

2009h

Error Signal 1

Fh RH

Braking Resistor Overheat

200Dh Digital Input Terminals Value (Bit Field)

6h @ Minor Fault (Alarm)

0h EF3

External Fault 3

200Eh Analog Input 36 Value (U1-15)

7h @ Major Fault

1h EF4

External Fault 4

200Fh PG Count Channel 2 (when PG-W2 is installed)

8h @ OPE Fault

2h EF5

External Fault 5

2010h Inverter Software ID (U1-14)

2000h

Status
Word

9h @Power Loss Ride Thru

200Ah

Error Signal 2

3h EF6

External Fault 6


WARNING!

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.