PROFIBUS-DP

®

Option Card

CM067

‰

Unpack the V7 PROFIBUS-DP Option and verify that all components are present and undamaged.

Part

Qty.

V7 PROFIBUS-DP Option Card Ring Kit

1

Mounting Bracket

1

M3×8 Screw

1

6” Ground Wire (150mm)

1

8.5” Ground Wire (220mm)

1

12.5” Ground Wire (320mm)

1

Installation Guide (IG.V7.12)

1

‰

Connect power to the drive and verify that the drive functions correctly. This includes running the
drive from the operator keypad. Refer to the V7 Technical Manual, TM.V7.01, for information on
connecting and operating the drive.

‰

Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at
least five additional minutes for the drive to be completely discharged. Measure the DC BUS
voltage and verify that it is at a safe level.

Align hole in
mounting bracket
with nib on front of
the V7 drive

Secure mounting
bracket to V7 drive
with M3x8 screw

Remove the CN2
protective cover by
carefully clipping
the three tabs

Option
mounting
bracket

C

N

2 Cover

‰

Prepare the drive for the V7 PROFIBUS-DP Option.

„

Remove the V7 operator keypad and terminal cover.

„

Remove the plastic protective cover from over the CN2 connector and install
the option mounting bracket provided on to the drive.

‰

Connect the ground wire provided to the ground connector on the back of the V7
PROFIBUS-DP Option
.

‰

Mount the V7 PROFIBUS-DP Option onto the drive

„

Align the CN1 connector on the back of the option with its mating CN2
connector on the front of the drive.

„

Simultaneously align the CN3 connector, the male RJ45 connector, on the back
of the option with the CN1 connector, the female RJ45 connector, on the front
of the drive.

„

Align the tabs on the option with their corresponding slots on the front of the
drive.

„

Press the option and the drive together until the tabs lock into their associated
slots.

„

Secure the option to the V7 drive by tightening the locking screw at the top-
center of the option.

„

Connect the ground wire from the V7 PROFIBUS-DP Option to ground terminal
on the V7 drive.

„

Reinstall the operator keypad and all drive covers.

CN1 - CN2

Tab

CN3 - Male RJ45
Connector

CN1 - Female
RJ45 Connector

Slot

Tab

Slot

E

Ground Terminal

Ground Wire

Indicator
LEDs

Profibus Cable
Connector

Termination Switch

S2 S1

Node Address
Switches

CN1 - Modular Plug
RJ45 Female

CN3 - Modular Plug
RJ45 Male

Ground Wire Connection

CN1
Connector

PWR

COMM

ERR

WD

Front

Back

Mounting Bracket

Ground Wires

E

E

E

E

E

E

12.5" (320mm)

8.5" (220mm)

6" (150mm)

M3x8 Screw

Locking Screw

Advertising