N2 Setup Parameters

u

N2 Serial Communication

This section describes parameters necessary to set up N2 communications.

n

Z3-01: Serial Communications Protocol Select

Selects the communications protocol.

No.

Name

Setting Range

Default

Z3-01

Serial Communications Protocol Selection

0 to 3

0

Setting 0: MEMOBUS/Modbus
Setting 1: N2
Setting 2: P1
Setting 3: BACnet

n

Z3-02: Serial Communications Node Address Select

Sets the drive slave address used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

Z3-02

Serial Communications Node Address Select

0 to FFH

1FH

Each slave drive must be assigned a unique slave address for serial communications to work. Slave addresses do not need to

be assigned in sequential order, but no two drives may share the same address.

n

Z3-03: Serial Communications Baud Rate Select

Sets the communication speed.

Note:

1. Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

Z3-03

Serial Communications Baud Rate Select

0 to 8

3

Z3-03

Communication Speed Z30

Z3–03

Communication Speed

0

1200 bps

4

19200 bps

1

2400 bps

5

38400 bps

2

4800 bps

6

57600 bps

3

9600 bps

7

76800 bps

8

115200 bps

n

Z3-04: Serial Communications Parity Select

Sets the parity used for communications.

Note:

Cycle the power after changing this parameter to enable the new setting.

No.

Name

Setting Range

Default

Z3-04

Serial Communications Parity Select

0 to 2

0

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n

Z3-05: Serial Communications Fault Select

Selects the action to take when a serial communications fault is selected. If communications is lost for more than the time

programmed in Z3-06, then a communication fault is detected.

Note:

Cycle the power after changing this parameter to enable the new setting.