KEB Command Using Multi-function Digital Input
Programming the KEB command to a multi-function digital input, KEB starts with the KEB Command
OR the drive’s DC bus voltage. The drive specifies the recovery from the power loss when these
signals are restored after the Power Loss Detection Relay Delay Time elapses, and re-accelerates
up to the former speed.
Note: Set KEB Starting Voltage (n048) to a lower value when using the multi-function digital input
KEB command. This will prevent the DC bus voltage detection circuit from activating KEB.
KEB Without a Braking Resistor
Behavior when deceleration stall prevention operates at deceleration (Stall Prevention during
Deceleration Enabled: n092 = 0)
Drive main circuit 
DC bus bar voltage 
Braking Transistor Operational Voltage or Deceleration 
←Stall Prevention Operational Voltage (n049) 
Drive output frequency
KEB Starting Voltage→ 
(n048) 
0
Power 
loss 
 ↓ 
During under 
voltage detection 
OFF
KEB Command
0
n019or n021acceleration ratio
OFF
ON
Power Loss Detection Relay Delay Time (n144)
OFF
OFF
ON
ON
OFF
During KEB 
operation 
OFF
KEB Deceleration ratio changeover time (n047)
KEB Deceleration Time 1 
 (n045)
KEB deceleration time 2 (n046)
RUN(FWD) command
ON
KEB Re-acceptance prohibition time (n145)
Drive main circuit
DC bus bar voltage 
Drive output frequency
KEB starting voltage→
0
Power Loss
 ↓ 
0
When deceleration stall prevention
operates at deceleration
↓
←Braking transistor operation voltage or
deceleration stall prevention operational
voltage(n049)
Deceleration ratio or deceleration time 
without KEB function →
Multifun
c
tion
In
p
ut
Mult
ifu
n
ction
Ou
tp
ut
<2> Depending on set value of KEB
re-acceleration time selection (n146)