Overview:

This software adds a DC Injection command as a multi-function input selection. The DC Injection
command causes DC current to flow in the motor windings, which aligns the motor poles and provides
holding torque.

Additional Multi-function Input Setting:

Setting Description

28

DC Injection Command


When n050 ~ n056 = 28, the corresponding input terminal (S1 ~ S7) is used for commanding DC
Injection.

Description of Functionality:


• The DC Injection command will be active under the following conditions: the inverter is ready (i.e. not

in program mode or in a fault state), no run command is present, and the output frequency is less
than the Minimum Frequency (n016).

• The DC Injection Current Level is set by the standard parameter n089 (as a percentage of inverter

rated current).

• The DC Injection at Start and DC Injection at Stop parameters n090 and n091 have priority over the

external DC Injection command.

• The External Baseblock command has priority over the external DC Injection command.

Timing Chart:

Run

Command

DC Injection

Command

Output

Frequency

DC Injection

DC Injection

10ms

Baseblock *


* To prevent the 10ms Baseblock at the end of deceleration, set DC Injection Time at Stop n090 = 0.1
sec.