3 New and Modified Software Functions

14

YASKAWA AMERICA, INC. TM.V1000SW.029 Traverse Application V1000 Custom Software Supplement

Figure 2

Figure 2 Master and Slave Output Diagram: Standard Operation

Implementation

Situation 1: Standard Operation

When programmed with the settings shown in

Table 10

, the Traverse software produces

output waveforms similar to the ones in

Figure 2

. Using these settings and a reference

frequency of 45 Hz, the master drive operates based on the triangle waveform with 9 Hz

peak amplitude. Because the waveform is centered on the 45 Hz reference frequency, the

master waveform oscillates between 36 and 54 Hz while in Traverse mode.

Table 10 Sample Operating Parameters

Parameter

Name

Setting

P1-01

Disturbed P1-05 Waveform Selection

1

P1-02

Disturbed Waveform Amplitude

20.0%

P1-03

Disturbed Waveform Jump

50.0%

P1-04

Negative Slope Time

5.0 s

P1-05

Positive Slope Time

4.0 s

Run

command

Frequency

reference

0

U7-02

Slave Absolute

Frequency

U7-02

Slave Base Frequency

U7-03

Slave Ripple

Frequency

E1-04 x 50% (Hz)

Speed Agree

Disturb UP Status

multi-function output

During Disturbed

multi-function output

P1-02 x

Freq. Ref.

P1-02 x

Freq. Ref.

P1-02 x

Freq. Ref.

P1-02 x

Freq. Ref.

P1-02 x

Freq. Ref.

P1-02 x Freq. Ref. x P1-03

P1-02 x Freq. Ref. x P1-03

2 - P1-03

P1-02 x Freq. Ref. x P1-03

2 - P1-03

P1-02 x

Freq. Ref.

P1-04

P1-05