Iqpump 7 ac drive, Simplex quick start procedure, Page 1 of 4

Advertising
background image

Fig. 3 Digital Operator

Next, push

2 times on the digital operator until

In this step, the iQpump is setup for a simplex pump
application using the Pump Quick Setup menu. Apply
power to the iQpump after all the electrical connections
have been made and the terminal cover has been
re-attached. At this point

DO NOT RUN THE MOTOR

the

digital operator should be reading as shown below in
Fig. 3.

FWD LED

ON

RUN LED OFF

01 Flashing

the digital operator shows the Pump Quick Setup Main Menu.

Next press

to start

the Pump Quick Setup procedure.

The Pump Quick Start Menu consists of the most important
parameters to setup your iQpump for use with your pump system.

Press to access a parameter, and use

to select the digit and use to change the

parameter value.

Press to save the value.

Press to go to the next parameter to continue the Pump

Quick Setup programming. When Quick Setup is completed, press

to exit the Pump Quick Setup menu and go to operation.

Note: Refer to Step 5 for a Pump Quick

Setup Parameter Overview.

Feedback

Value

IMPORTANT: Enter service factor amps (SFA) when using an
iQpump with a submersible pump motor.

STOP LED ON

Step

1

iQpump Model Identification

and Mounting

To make sure you received the correct model, it is essential to

verify the iQpump nameplate with your order and make sure

the iQpump has the correct rating so it can be used with your

motor. Please check the nameplate information as shown in

the example below.

·

Check that the available power will meet the

input power

requirements.

·

Ensure that the

output power from the iQpump is

compatible with the pump motor requirements.

Mounting the iQpump

·

In the case of systems with more than one iQpump, follow
the above procedure for each iQpump and pump motor.

Open Chassis

NEMA 1

The mounting of the iQpump is extremely important
regarding environment and accessibility. Depending on your
system, there are various models available and the mounting
dimensions (footprint) may be different. Because the
mounting procedure is fairly extensive, it is beyond the scope
of this document; the user is referred to the iQpump User
Manual (Document No. TM.iQp.06) received with the
iQpump,

Section 1 Physical Installation. Match the model

that you received and follow the procedure described in the
manual to ensure a safe and functional installation. In cases
where the system has more than one iQpump, refer to the
proper clearances required for adequate ventilation.

Please

pay particular attention to:

·

The clearances to be maintained around the enclosure
for adequate ventilation.

·

The environmental specifications such as avoiding
excessive dampness, extreme temperatures, chemical
exposure, corrosive areas, etc. to avoid damage to the
equipment and to maintain safety.

Removing and Attaching the Terminal Cover

Improper removal of the iQpump terminal cover as well as
front cover can cause extensive damage to the iQpump. To
avoid damage to these items, please pay particular attention
to the iQpump User Manual, Document No. TM.iQp.06,
Section 1.8, R

Removing and Attaching the Terminal Cover.

Drive Model

Number

Input Power

Rating

Output Power

Rating

Serial

Number

UL File

Number

Drive Spec

Number

Weight

0034

WARNING DO NOT CONNECT ANY OF THE

FOLLOWING TERMINALS TO EARTH GROUND

B1

B2

-

+

+1

+2

R/L1 S/L2 T/L3

-

+ 1

+ 2

B1

B2

U/T1 V/T2 W/T3

NOT USED

3Ø Induction

motor

Use L1, L2, L3 for

3Ø Input Power

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

To change direction of

pump motor rotation
swap any two of the

three motor leads

(See Step 2)

L1 L2 L3

Fig. 1 Input Power and Output Motor Electrical Connections for
Models: 20P4 to 2018 and 40P4 to 4018

NOT USED

3Ø Induction

motor

Connect
frame to

ground

Input

Protection

(Fuse or Circuit

Breaker)

To change direction of pump
motor rotation swap any two

of the three motor leads

(See Step 2)

Fig. 2 Input Power and Output Motor Electrical Connections for
Models: 2022 & Larger and 4030 & Larger

R/L1

R1/L11

S/L2

S1/L21

T/L3

T1/L31

U/T1

V/T2

W/T3

-

+ 1

+ 2

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to

chassis
ground

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to

chassis
ground

Use L1, L2 for

1Ø Input Power

Use L1, L2, L3 for

3Ø Input Power

L1 L2 L3

Use L1, L2 for

1Ø Input Power

Connect to

chassis ground

Fig.1 & 2 below show the electrical connections for the
input power and motor terminals for various iQpump
models. Select the proper diagram for the model you are
installing (see Step 1). WITH POWER OFF make the
appropriate connections.
Make sure to follow good wiring practices and all
applicable codes. Ensure that the equipment is
grounded properly as shown.

DANGER; LETHAL VOLTAGES ARE PRESENT- Before
applying power to the iQpump, ensure that the
terminal cover is fastened and all wiring connections
are secure. After the power has been turned OFF, wait
at least five minutes until the charge indicator
extinguishes completely before touching any wiring,
circuit boards or components.

!

*

* Make sure the iQpump has been properly sized for single phase input power.

*

Connect Pump Motor and

Line Power

Step

2

Step

3

Control Wiring

Step

4

Pump Quick Setup

The following
procedure is a
supplement to
other
documentation
supplied with this
equipment and
will guide the user
in properly wiring
the iQpump and
motor. It will also
show the user
how to configure
the iQpump for a
simplex pump
application.

Danger:
Improper wiring
can and will
cause
bodily
harm as well as
damage to the
equipment.

When installing
the system, be
sure to follow
good wiring
practices and all
applicable codes.
Ensure that the
mounting of the
various
components are
secure and that
the environment,
such as extreme
dampness, poor
ventilation, etc.
will not cause
system
degradation.

Please read this
cheat sheet and
other
documentation
provided with
the iQpump
thoroughly
before
attempting any
installation.

Page 1 of 4

iQpump 7 AC Drive

(Software 0034)

Simplex Quick Start Procedure

The iQpump is D

DEFAULT SETUP TO START/STOP FROM THE

KEYPAD (digital operator). If this is the preferred start/stop
method, then continue to the feedback signal connection section.
Please refer to the wiring diagram below to start/stop the iQpump
using an external switch or contact.

This step shows how to connect control wiring and feedback signal
to the iQpump. Before making any control connections, M

MAKE

SURE POWER TO THE iQpump IS TURNED OFF! Next remove
the terminal cover to gain access to the control terminals. (Step 1.)

SELECT START / STOP CONTROL METHOD

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

2-Wire Control

Use for permanent contacts

iQpump User Control Terminals

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Connect switch or contact to
terminal S1 and terminal SN

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

3-Wire Control

Use for momentary contacts

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Connect momentary contacts
to terminal S1, S2 and SN

Normally Open

Normally Closed

To use 3-Wire Control first
initialize the iQpump using

parameter A1-03 = 3330

(Refer to TM.iQp.06)

FEEDBACK SIGNAL WIRING (TRANSDUCER)

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

For use with 3-Wire, 0 – 10V Transducer

iQpump User Control Terminals

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Brown or Red: +Power (1)

O
F
F

1

2

S1-2 in ON

Position

S3

S5 S6 S7 FM AC AM IG

S2

S4

S1

S+ S-

SP

A2 +V AC

AC

SC

A1

SN

R+ R-

Brown or Red: +Power (1)

Black or White Output
0 – 10V (3)

O
F
F

1

2

S1-2 in OFF

Position

Blue or Black
Common Signal (2)

Black: Output
4 – 20mA (2)

Cable

Type

DIN

Type

For use with 2-Wire, 4 – 20mA Transducer

Important Note: Signal colors and numbering may vary
depending on feedback device used.
Please consult feedback device manual.

!

Cable
Shield

Cable
Shield

E(G)

E(G)

(Factory Default)

E(G)

Cable
Shield

Cable
Shield

E(G)