M a i n t e n a n c e / T r o u b l e s h o o t i n g
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
Page 45
9.5
Messages on the display and the “Fault” LED
Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The minimum triggering 
levels are determined by standards. The inverter must switch off if the permitted values are undershot or exceeded.
9.5.1
Display of status and fault messages
Display
Fault LED (red)
FS (fault status)
ON
•
Fault signal relay has switched.
•
Feed-in was ended due to a fault.
OS (operating status)
OFF
•
The fault signal relay deenergizes again.
•
The inverter feeds back into the grid again 
after a country-specifi c time period.
On the display you can fi nd details regarding the fault or operating status or the data that was recorded through the 
RS485 interface.
Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.
Status
Display
Explanation
Action
OS
1
Waiting for feed-in
Self-test: The grid parameters and 
generator voltage are being checked.
-
-
OS
2
Generator voltage 
too low
Insuffi
cient generator voltage and
power,
status before the transition to night 
shutdown
-
-
OS
8
Self-test
Checks the shutdown of the power 
electronics as well as the grid relay 
before feed-in mode
-
-
FS
10
Temperature in
unit too high
In case of overheating, the inverter 
switches off . Possible causes: 
•
Ambient temperature too high
•
Fans covered
•
Inverter defect
 Cool off the area
around the inverter.
 Uncover the fans.
 Notify your
authorised 
electrician.
B
B
E
OS
11
Measured values
Power limitation: If the generator power is too high, the inverter 
limits itself to the maximum power (e.g. around noon if the generator 
capacity is too large). 
FS
17
Shutting down 
Powador-protect
The activated grid and system 
protection has been tripped.
 Wait for
reactivation.
 Notify your
authorised 
electrician if the 
fault occurs several 
times.
E
FS
18
Resid. current 
shutdown
Residual current was detected. The 
feed-in was interrupted.
 Notify your
authorised 
electrician.
E
Table 6:
Operating statuses and fault messages on the display