Operating Instructions Powador XP100-HV

F a u l t s a n d W a r n i n g s

F a u l t s a n d W a r n i n g s

Faults

Code

Message

Warning description

Possible problem and solution(s)

1

PV Over Voltage

PV voltage exceeds the param-

eter

Problem

• The voltage of the solar generator is too

high

Solution(s)

• Check the input voltage

• Check module wiring and system

2

PV Over Current

PV current exceeds the parame-

ter

Problem

• The current of the solar generator is too

high

• PV system wiring short

Solution(s)

• Check the input current

• Check module wiring and system

4

CB10 (PV CB) Trip

PV side circuit breaker (CB10)

tripped

Problem

• CB10 disconnect switch is open

• Auxiliary switch is inoperable, CB10 con-

tactor failed closed

Solution(s)

• Check the wiring connection

• Change the CB10, replace CB10 contactor

5

PV Polarity Failure

Polarity (+, -) of PV side is
reversed

Problem

• Polarity of PV side is reversed

Solution(s)

• Check the wiring connection and change
if necessary

6

Ground Fault

PV side ground fault

Problem

• DC & ground are shorted causing the

GFDI fuse to open

Solution(s)

• Check the solar generator for a ground

fault and Replace the GFDI Fuse

10

Inv. Over Voltage

Over voltage on the inverter side Problem

• The inverter voltage is too high

Solution(s)

• Check the inverter voltage

• Check the inverter parameter

Table 8: Faults