Operating Instructions Powador XP100-HV

Page 51

P a r a m e t e r

P a r a m e t e r

8 Parameter

The KACO XP100-HV parameters are pre-confi gured for operation. These parameters make KACO XP series invert-
ers to be powerful, effi

cient and perfectly suited for implementing large-scale PV plants.

The KACO XP100-HV parameters are subdivided into ten:

•

PV

Array

Setting values for MPPT control and startup of inverter

•

Inverter

Setting values for inverter rate and cabinet temperature

•

Grid

Setting values for abnormal and rated levels of grid

•

Time

Setting values for the current time

•

Digital

Setting values for digital interface

•

Analog

Setting values for analog interface

•

Controller

Setting values for inverter control

•

Trace

Setting values for inverter fault analysis

•

Off set

Setting values for sensing off set calibration

•

Gain

Setting values for sensing gain calibration

8.1

PV Array Parameters

Parameters

Units

Ranges

Descriptions

Default

MPPT Enable

N/A

On(1), Off (0)

“On” represents what MPPT is operating

1

MPPT V Maximum

V

dc

0 ~ 900

Maximum voltage to run MPPT

830

MPPT V Start

V

dc

450 ~ 800

MPPT wake-up voltage

600

MPPT T Start

sec

0 ~ 600

Time delay for MPPT wake-up

300

MPPT P Stop

W

0 ~ 10000

Disconnect inverter from Grid when PV output

power is lower than the setting value of {MPPT P
Stop}.

1000

MPPT T Stop

sec

0 ~ 600

Time delay while inverter decides if PV output

power is lower than the setting value of {MPPT P
Stop}.

30

MPPT V Minimum

V

dc

200 ~ 800

Minimum voltage to run MPPT

410

Table 10: PV Array Parameters