Operation – Eaton Electrical 9130 User Manual

Page 16

Advertising
background image

Page 16

9130 UPS-EN

4. Operation

Power Strategy

[Normal] [High Efficiency]
See "Setting Power Strategy" on page 19.

Normal

Automatic start delay

[No Delay] [Disabled] [1,2,...,32767 s]
To define if the load turns automatically on, with
the delay set after the utility return, if it has been
shutdown by:
- signal input with auto-restart option
- an XCP command with autorestart option
- battery under voltage state, or automatic on
battery shutdown command.

No Delay

Automatic on battery
shutdown

[Disabled] [No Delay] [1,2,...,32767 s]

To define if the load turns automatically off when
"UPS on battery" state activates.

Disabled

Start on Battery
NOTE: utility must be
present and output
enabled at initial UPS
startup.

[Enabled] [Disabled]
After initial startup, battery voltage must exceed
2.10 volts per cell to start on battery.

Enabled

Energy Saving Mode

[Disabled] [50W] [100W] ... [1000W]
UPS output is turned off (after 5 min) if the UPS is
on battery and output power is below the selected
level.

Disabled

Remote Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

No Delay

Delayed Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

120 s

On Battery Notice Delay

[0] [1s] [2s]...[99s]

5 s

Site Wiring Fault Alarm

[Enabled] [Disabled]
An active site wiring fault alarm prevents startup or,
if operating, forces operation to Battery mode and
disables bypass.

Enabled

Bypass Voltage Low
Limit*

[-4%] [-5%] ... [-20%] of nominal

-15 % of nominal

Bypass Voltage High
Limit*

[+4%] [+5%] ... [+20%] of nominal

+10 % of nominal

Qualify Bypass*

[Never] [When in Spec] [Always on UPS Fault]
[Always]

When in Spec

Synchronization Window* [Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±2.0 Hz]

[±3.0 Hz]

±3 Hz

Unsynchronized
Transfers*

[Enabled] [Disabled]

Enabled

Number of Battery Strings [0] [1] [2] ... [10]

See "Configuring the UPS for EBMs" on page 18.

1

Battery Charge Mode

[ABM Cycling] [Constant]

ABM Cycling

Temperature
Compensated Charging

[Enabled] [Disabled]
If Disabled, the default charger voltages for 25 °C
(77°F) are assumed.

Enabled

Battery Charge % to
Restart

[Not Checked] [10] [20] ... [100]
If a percentage is selected, automatic restart (if
enabled) occurs when the battery’s charge reaches
the selected level.

Not Checked

Battery Low Alarm

[Immediate] [2 min] [3 min] [5 min]
The "Battery Low" alarm triggers when the set
amount of backup time (approximately) remains in
the batteries. If set to Immediate, the alarm activates
at the same time as the "UPS on Battery" notice.

3 min

Automatic Battery Support
Tests

[Enabled] [Disabled]
See "Running Automatic Battery Tests" on page 20

Enabled

Deep discharge protection [Enabled] [Disabled]

Protection against deep discharge. If disabled, Eaton
warranty will be void.

Enabled

Start on Bypass

[Disabled] [Enabled]
During start up sequence, transfer first on Bypass
(for 5~15 seconds) then transfer online.

Disabled

Ambient Temperature
Warning

[Enabled] [Disabled]

Enabled

Predictive Maintenance
Notices

[Enabled] [Disabled]

Enabled

Remote Power-off (RPO)
Input Polarity

[Open] [Closed]

Open

* See "Configuring Bypass Settings" on page 19.