Specifications, 1 model specifications, English – Eaton Electrical 9130 User Manual

Page 31

Advertising
background image

Page 31

9130 UPS-EN

ENGLISH

7. Specifications

7.1

Model Specifications

This section provides the following specifications:

Communication options

Model lists

Weights and dimensions

Electrical input and output

Environmental and safety

Battery

Table 13. Communication Options

Communication Bay

(1) available independent communication bay for connectivity cards

Compatible
Connectivity Cards

Connect UPS-MS Web/SNMP Card
Relay Interface Card

Communication Ports

RS-232 (DB-9): 1200–9600 bps
USB: 9600 bps

Signal Inputs

(4) programmable signal inputs (signal and signal return) for indicating
building alarms or other use

Relay Output Contacts

(1) three-pole connector with (1) contact closure

Table 14. Extended Battery Module Model List

EBM Model

Configuration

Battery Voltage

For Power Ratings

PW9130N6000T-EBM

Tower

240 Vdc

5000–6000 VA

Table 15. UPS Model List

Model

Power Level

Rear Panel Diagram

PW9130i5000T-XL

5000 VA / 4500 W

Figure 21 on page 21

PW9130i6000T-XL

6000 VA / 5400 W

Figure 21 on page 21

Table 16. Weights and Dimensions

Model (Tower UPS)

Dimensions (H W D)

Weight

PW9130i5000T-XL
PW9130i6000T-XL

575* 242 542 mm (22.64”* 9.53” 21,34”) 105 kg (231.5 lb)

Model (Tower EBM)

Dimensions (H W D)

Weight

PW9130N6000T-EBM

575* 242 542 mm (22.64”* 9.53” 21.34”) 120 kg (264.55 lb)

Table 17. Electrical Input

Nominal Frequency

50/60 Hz auto-sensing

Frequency Range

40–70 Hz before transfer to battery

Bypass Voltage Range

+10 / -15 % of nominal (default)

Noise Filtering

MOVs for normal and common
mode noise

Advertising