Specifications – Eaton Electrical 9130 User Manual

Page 32

Advertising
background image

Page 32

9130 UPS-EN

7. Specifications

Table 18. Electrical Input

Model

Default Input
(Voltage/Current)

Selectable Input
Voltage Range

Voltages
at 100 % Load

PW9130i5000T-XL

230 V / 21.7 A

200*, 208*, 220, 230, 240

180–276 Vac

PW9130i6000T-XL

230 V / 26.1 A

200*, 208*, 220, 230, 240

180–276 Vac

208 V are derated by 10 %.

Table 19. Electrical Input Connections

Model

Input Connection

Input Cable

PW9130i5000T-XL
PW9130i6000T-XL

Hardwired

None

Table 20. Electrical Output

All Models

Normal Mode

Battery Mode

Voltage Regulation

±2 %

Nominal output voltage ±3 %

Efficiency

> 98 % (High Efficiency mode),
> 94 %

> 92 %

Frequency Regulation

Sync with line ±3 Hz of nominal line
frequency (outside this range: ±0.1 Hz
of auto-selected nominal frequency)

±0.1 Hz of auto-selected nominal
frequency

High Voltage Models

Nominal Outputs

200/208/220/230/240V (voltage configurable or auto-sensing)
5000/6000 VA 4.5/5.4 kW

Frequency

50 or 60 Hz, autosensing or configurable as a frequency converter

Output Overload

100–102 %: Activates Overload alarm (Level 1)
102–129 %: Load transfers to Bypass mode after 2 minutes (Level 2)
130–149 %: Load transfers to Bypass mode after 30 seconds (Level 3)
≥ 150 %: Load transfers to Bypass mode after 100 ms (Level 4)

Output Overload
(Bypass Mode)

100–109 %: Activates Overload alarm (Level 1)
110–129 %: UPS shuts down after 5 minutes (Level 2)
130–149 %: UPS shuts down after 30 seconds (Level 3)
≥ 150 %: UPS shuts down after 300 ms (Level 4)

Voltage Waveform

Sine wave

Harmonic Distortion

< 3 % THD on linear load;
< 5 % THD on non-linear load

Transfer Time

Online mode: 0 ms (no break)
High Efficiency mode: 10 ms maximum (due to loss of utility)

Power Factor

0.9

Load Crest Factor

3 to 1

Table 21. Electrical Output Connections

Model

Output Connections

Output Cables

PW9130i5000T-XL
PW9130i6000T-XL

Hardwired

None