Clearance requirements, Connecting the dc load cables, Dc load cable specifications – Eaton Electrical APR48 User Manual

Page 16

Advertising
background image

Data Power Solutions Quick Start Guide

16

Copyright © 2006-2009 Eaton Corporation. All Rights Reserved.

10640205 February 2009

Notas importantes referidas a los sistemas de montaje en un rack:

Si este sistema de energía dc está instalado en un montaje cerrado o para varias unidades,
asegúrese de que la temperatura ambiente sea inferior a los 40°C.

Asegúrese de que el flujo de aire no esté restringido.

Asegúrese de que el peso del sistema sea adecuado y de que tenga un soporte parejo.

Tome nota de la corriente de entrada CA máxima establecida en la placa de características.
Asegúrese de que el suministro CA tenga una capacidad nominal correcta.

Asegúrese de mantener una conexión a tierra confiable. Compruebe cuidadosamente la
continuidad a tierra desde el circuito derivado al sistema de energía CC.

Clearance Requirements

All APS dc power systems (rack-mounted and desktop versions) require the following
minimum clearances:

Front and Rear Clearance – 50mm (2”) from walls and other equipment, required for
optimum system cooling and access.

Top and Bottom Clearance – None

Connecting the DC Load Cables

Before you start connecting the dc load and battery cables (if applicable) to an APS dc power
system, please read the following DC Installation Practices:

To easily distinguish between positive and negative load cables, we recommend using
cables with different colors (as specified by local wiring regulations). The same applies to
battery cables (if applicable).

To reduce inductive coupling, separate dc load, battery and communications cabling
from ac supply cables. If the cables have to cross, run them at right angles to the ac
supply cables.

In order to minimize parasitic cable inductance and reduce electromagnetic interference
(EMI), all dc load cables should be routed in close proximity to one another, and large
current loops should be avoided. The same applies to battery cables (if applicable).

Eight dc outlets (labeled 1 to 8) are available for connecting your equipment power
cables to the APS dc power system. Each dc outlet is protected by a corresponding 6A or
25A circuit breaker (accessible from the dc distribution at the front). The current rating of
the corresponding circuit breaker determines the current rating of a dc outlet. The dc
outlets are floating to meet the isolation requirements for powering Power over Ethernet
IEEE802.3af compatible devices. In non-Power over Ethernet applications the positive or
negative output of the dc outlets can be referenced to earth, if required.

DC Load Cable Specifications

No dc load cables are supplied with APS dc power systems. dc load cables are sized
differently, depending on whether you connect to 6 A or 25 A dc outlets. All dc load cables
must meet the following specifications and no other cable sizes must be used.

6A dc Outlets:

UL 1015, 18 AWG (1mm), multi-strand cable

25A dc Outlets:

UL 1015, 12 AWG (4mm), multi-strand cable

Cable Length:

3m (10 feet) maximum