Specifications 15

Emerson Energy Systems

Rectifier 200I/48

NT5C05C Installation and User Manual

Table 4 - Ambient conditions for the rectifier

Operating
conditions

A minimum airflow clearance of 2 inches ( 5 cm ) is
required at the rear of the rectifier.

The rectifier will operate properly under the following
conditions.

Temperature: 32°F to 122°F ( 0°C to +50°C )

32°F to 104°F ( 0°C to +40°C ) with air
filters

Humidity:

0 to 95% RH ( non-condensing ) at 4
kPa max. equiv. to 7,000 ft. ( 2,100 m )
above sea level

Transportation
conditions

During transportation, the rectifier can be subjected to
the following conditions without sustaining damage.

Temperature: –67°F ( –55°C ) for 16 hours

140°F ( +60°C ) dry heat

Humidity:

0 to 95% RH ( non-condensing ) at
4 kPa max.

Vibration:

38 mm / s max. ( 10 Hz to 30 Hz )
sinusoidal, 18-inch ( 457 mm ) drop
when packaged

Pressure:

12 kPa min. equiv. to 49,212 ft.
( 15,000 m above sea level)

Temperature shock :

58°F to 140°F (

50°C to 60°C )

Storage conditions

During storage, the rectifier may be subjected to the
following conditions without damage :

Temperature: –67°F ( –55°C ) for 16 hours to 140°F

( +60°C ) dry heat

Humidity:

0 to 95% RH ( non-condensing ) at
4 kPa maximum

The rectifier contains aluminum electrolytic capacitors
that have a shelf life of five years or greater at the
maximum rated storage temperature.