Troubleshooting – Emerson 200I/48-NT5C05C User Manual

Page 53

Advertising
background image

53

Emerson Energy Systems

Rectifier 200I/48

NT5C05C Installation and User Manual

7. Troubleshooting

Table 16 - Diagnosing system faults

Fault symptom

Possible causes

The RFA LED is lit.

•

No ac input or input is out of bounds ( ac ON
LED is extinguished ).

•

AC Input / dc output circuit breaker is open.

•

The rectifier has received an HVSD signal from
the controller, or a TR signal is present.

•

An internal high voltage shutdown ( HVSD ) has
occurred.

•

Two cooling fans or fuses have failed.

•

The inrush fuse has blown.

•

The dc circuit breaker is open.

•

A thermal shutdown has occurred.

•

Ambient air temperature is high.

•

Air inlet / outlet air is blocked, or the air filter is
clogged.

•

A rectifier is in 'Start Time Delay' mode and the
RFA will cease when the required time delay has
elapsed.

•

Defective rectifier.

The HVSD LED is lit.

•

The internal high voltage shutdown point is set
to low ( below the float or equalize setting ).

•

The controller triggered a remote HVSD.

−−−−

continued

−−−−