54 Troubleshooting

UM5C05C P0745680 Standard 6.00 October 2001

Emerson Energy Systems

Table 16 – Diagnosing system faults

Fault symptom

Possible causes

The AC ON LED is not
lit.

•

No ac input voltage.

•

The input circuit breaker is open.

•

AC voltage is present but is out of operational
limits. The unit will restart when the ac returns to
the operating level.

•

AC has just been applied and the rectifier will
momentarily start ( after an inrush control
delay ).

The FAN ALM LED is
lit.

•

The fuse of one or both fans has blown.

•

One or both fans have failed.

Note 1 : If a single fan failed or a fuse blew, the

rectifier will continue to operate while
triggering a local and remote FAN ALM.

Note 2 : If two cascaded fans failed or both fuses

blew, the rectifier will shut down and
trigger local and remote RFA alarms.

The SEN FAIL LED is
lit.

•

One, or both, remote sense leads is
disconnected.

•

Excessive impedance in one or both sense
leads.

•

The dc circuit breaker is open but the unit is in
remote sense.

The CL LED is lit.

•

The output load requirement exceeds the total
rectifier capacity.

•

With paralleled units, the float or equalize is
maladjusted causing one or more units to carry
the load.

•

The unit is in "equalize" mode and paralleled
units are not.

•

The remote sense lead has excessive
impedance on one or more rectifiers.

•

The system batteries are in recharge mode after
an ac outage.

•

The current share mode selection is not the
same for all units.

•

The forced share line is disconnected ( in FLS
only ).

—end—