8

Initial Installation

QUALIFIED INSTALLERS ONLY

S

TRAIGHT

V

ERTICAL

I

NSTALLATION

:

Figure 5: Straight vertical installation.

This basic venting configuration shown are rough

guidelines only. Follow national and local codes for

other installation options.
For the best venting performance, we recommend a

total vent height in the range of 10 feet (3.0 m) to 30

feet (9.1 m). The total horizontal length depends on

the number of elbows used; a 90° elbow accounts for

5 feet (1.5 m) of the horizontal run.

The venting should never slope down, a minimum 1⁄4

inch (0.6 cm) rise is needed for every 2 feet (61 cm)

of horizontal is recommended.

If practical, it is best to locate the appliance to permit

the use of shorter horizontals and fewer elbows.

Number of 90° elbows Maximum total horizontal

length allowed

2

20 feet (6.1 m)

3

13 feet (4.0 m)

4

6 feet (1.8 m)

5

0 feet (0 m)

Note: Using two (2) 45° elbows is equivalent to using

one (1) 90° elbow.

The venting rise should be a minimum of 1 foot (0.31

m) from the top of the unit before any horizontal run

are used.

Table 1. 90° elbows allowed verses the

horizontal length.