Table 35
Estimated battery run time, minutes
UPS Rating/Model
Number of Cabinets
1
2
3
4
40kVA UPS
UPS12-100MR
5
18
32
47
UPS12-150MR
13
33
53
75
UPS12-210MR
21
51
81
123
60kVA UPS
UPS12-100MR
-
9
18
27
UPS12-150MR
7
19
33
47
UPS12-210MR
11
31
51
73
80kVA UPS
UPS12-100MR
-
5
11
18
UPS12-150MR
-
13
22
33
UPS12-210MR
6
21
36
51
100kVA UPS
UPS12-100MR
-
-
8
12
UPS12-150MR
-
9
17
25
UPS12-210MR
-
15
27
38
120kVA UPS
UPS12-100MR
-
-
5
9
UPS12-150MR
-
7
13
19
UPS12-210MR
-
11
21
31
Advertising