4 output dry contacts, Table 4 output dry contact relays, Output dry contacts – Emerson Liebert NX 480V User Manual

Page 27: Figure 9, Table 4, Output dry contact relays

Advertising
background image

Electrical Connections

19

2.3.4 Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 9 and Table 4).

Figure 9

Output dry contacts and EPO wiring for firmware before M170

Table 4

Output dry contact relays

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.

J21.2

INV_O

Inverter mode relay. Normally open. Closed when UPS is in inverter mode.

J21.3

INV_S

Inverter mode relay center

J21.4

INV_C

Inverter mode relay. Normally closed. Open when UPS is in inverter mode.

J25.2

ACF_O

Main input fault relay. Normally open. Closed when main input is in fault.

J25.3

ACF_S

Main input fault relay center

J25.4

ACF_C

Main input fault relay. Normally closed. Open when main input is in fault.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded

for maximum runs between 82 and 197 feet (25-60m), respectively.

J25

ACF

_O

AC

F

_S

AC

F

_C

J21

IN

V

_C

IN

V

_S

IN

V

_O

X1

J13

BF

P

_C

BF

P

_S

BF

P

_O

NOTE: The black square on each slot

indicates Pin 1.