3 bcb control interface, Table 3 bcb control interface, Bcb control interface – Emerson Liebert NX 480V User Manual

Page 26: Figure 8, Table 3

Advertising
background image

Electrical Connections

18

2.3.3 BCB Control Interface

J10 is the BCB box interface.

Figure 8

Jumper connection for BCB interface without a battery interface board

Table 3

BCB control interface

Position

Name

Description

J10.1

DRV

BCB Driver Signal

J10.2

FB

BCB Contact State

J10.3

GND

Power Ground

J10.4

OL

BCB On-Line - Input - This pin will become active when

BCB interface is connected. (N.O.)

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded

for maximum runs between 82 and 197 feet (25-60m), respectively.

NOTE
If a BCB interface is connected and a battery interface board is not used, a jumper

needs to added between Pin 3 and Pin 4.

UPS Monitoring Board

J10

OL

DRV

GN

D

FB

Battery Circuit Breaker

OL

Aux – N.O.

Aux – N.O.

Advertising