Technical characteristics, Rotary disconnect switches – Eaton Electrical Disconnect Switches User Manual

Page 17

Advertising
background image

16

For more information visit us at: www.eatonelectrical.ca

December 2004

Technical Characteristics

Table 14. CSA Technical Characteristics

Table 15. CSA/UL Technical Characteristics C, V, S & F Frame Non-Fused and Fusible

2-pole in series.

3-pole in series.

15 x 15 shaft for non-fusible and 10 x 10 shaft for fusible, 400A

DC rating on non-fusible 600A only, no DC rating for 600A fusible.

Values on left = non-fusible. Values on right = fusible.

Description

R-Frame

W-Frame

Catalogue Number

Catalogue Number

C362NR30MD /C362TR30MD C362NR40MD /C362TR40MD C362NW60MD /C362TW60MD

C362NW80MD /C362TW80MD

Rating Ampere

30A

40A

60A

80A

CSA C22.2#14/CEC Rule 28-602/ (3)(b)

CSA

CSA

CSA

CSA

Short Circuit Rating kA with Fuses

10

10

10

10

Fuse Class

J

J

J

J

Fuse Rating (A)

60

60

100

100

Maximum CSA

120V AC

2

3

5

7.5

Horsepower

208V AC

5

7.5

10

15

Ratings (3-Phase)

220 – 240V AC

7.5

10

15

20

440 – 480V AC

15

20

30

40

600V AC

20

25

40

50

Maximum CSA
Horsepower
Ratings (1-Phase)

120V AC

1.5

2

2

3

208V AC

2

3

5

7.5

240V AC

3

3

7.5

10

480V AC

7.5

7.5

15

20

600V AC

10

10

20

30

Electrical Endurance

(Operation Cycles)

6000

6000

6000

6000

Mechanical Endurance (Operation Cycles)

6000

6000

6000

6000

Terminal Lugs

Wire Size

#14 – #4

#14 – #4

#14 – #1

#14 – #1

Wire Type

Cu

Cu

Cu

Cu

Weight in Lbs. (kg)

.44 (.20)

.44 (.20)

.66 (.30)

.66 (.30)

Catalogue Number

C Frame

V Frame

V Frame

V Frame

V Frame

S/V Frame

S/F Frame

S/F Frame

S Frame

S Frame

C362UC30
C362UC30CT
C363UC30JT

C363UV30C
C363UV30J
C363UV30CT
C363UV30JT

C362UV60
C363UV60J
C363UV60JT

C362UV100
C363UV100J
C363UV100JT

C362UV200
C363UV200J
C363UV200JT

C362US400
C363UV400J
C363UV400JT

C362US600
C363UF600J

C362US800
C363UF800L

C362US1000 C362US1200

Rating Ampere

30

30

60

100

200

400

600

800

1000

1200

CSA C22.2 #4/UL98

CSA/UL

CSA/UL

CSA/UL

CSA/UL

CSA/UL

CSA/UL

CSA/UL

CSA/UL

CSA/UL

CSA/UL

Short Circuit Rating kA
with Fuses

50

CC-100
J-200

200

200

200

200

200

100/200

100

100

Fuse Class

CC / J

CC / J

J

J

J

J

J

L

L

L

Fuse Rating (A)

30

30

60

100

200

400

600

800

1000

1200

Maximum UL
Horsepower
(3-Phase)

240V AC 7.5

7.5

15

30

60

125

200

250

250

250

480V AC 15

15

30

60

125

250

400

500

500

500

600V AC 20

20

50

75

150

350

350

500

500

500

DC 125V 3

3

3

7.5

15

20

20

DC 250V 5

5

10

20

40

50

50

Electrical
Endurance

(Opera-
tion
Cycles)

6000

6000

6000

6000

6000

1000

1000

500/1000

➄ 500

500

Mechanical
Endurance

(Opera-
tion
Cycles)

10,000

10,000

10,000

10,000

8000

6000

6000/
5000

3500/
5000

3500

3500

Shaft Size
Square

Inches
(mm)

.2 x .2
(5 x 5)

.4 x .4
(10 x 10)

.4 x .4
(10 x 10)

.4 x .4
(10 x 10)

.4 x .4
(10 x 10)

.59 x .59
(15 x 15)/
.4 x .4
(10 x 10)

.59 x .59
(15 x 15)

.59 x .59
(15 x 15)

.59 x .59
(15 x 15)

.59 x .59
(15 x 15)

Switch Operat-
ing Torque

lb. in.

21

88

88

88

106

320/132

320

320

320

320

Terminal Lugs
Wire Size Min-
Max

Non-
Fused

#14 – #10

#14 – #10

#10 – #3

#10 – #3

#6-– 3/0

(2)#2-(2)
600mcm

(2)#2-(2)
600mcm

(3)#2-(3)
600mcm

(3)#2-(3)
600mcm

(4)#2-(4)
600mcm

Fusible

#14 – #10

#14 – #10

#10 – #3

#14 – 2/0

#6-– 3/0

(2)#2-(2)
600 mcm

(2)#2-(2)
600mcm

(3)#2-(3)
600 mcm

Weight in Lbs. (kg)

1.1 (.50)

1.1 (.50)

2.0 (.91)

2.5 (1.1)

4.4 (2.0)

8.8 (4.0)

9.9 (4.5)

22.0 (10.0)

28.6 (13.0)

30.8 (14.0)

Rotary Disconnect Switches