4.19. Exiting alarm condition

In case of an alarm intervening, to restore the normal operation of the

stove press the on/off key for a long time. After a short verification

phase if the cause that caused the alarm does not persist, the stove

leaves the alarm status and it may restart.

4.19.1. Shutdown of the stove

NEVER open the appliance door whilst the stove is

either in the initial startup or on its shut down cycle,

pellets will still be smoldering or therefore volatiles

may be present.

ATTENTION!
If during operation or initial ignition you encounter

smoke spillage in to the room from the appliance or

the flue then please switch off the appliance, ventilate

the room and contact the installation / service

engineer immediately.


The following things can cause stove shutdown:

Overheating of the stove body (“A03”)

Overheating of the smoke (“A04”)

During the function of the stove, an uncontrolled air intake

occurred in the combustion chamber or an obstruction in the flue

pipe. (“A05”)

Boiler overheating (“A18”)

WHAT TO DO:
When the stove is cold: if the message “A03” appears: The structure is

too hot because the product has been operating for too long at

maximum power, or it is poorly ventilated, or the air fans are faulty
When the stove is sufficiently cold, press button B of the control panel

to cancel the alarm A03. Once the alarm is cancelled it is possible to

relight the stove normally.

If the alarm “A04” appears the stove shutdown in automatic, leave it

to cool down for a few minutes and then re-light. Cancel the alarm and
re-light.
If the alarm “A05” appears: it is caused by prolonged opening of the

fire door or by substantial air infiltration (e.g. smoke fan inspection plug

missing). If not caused by these factors control and if necessary clean

the smoke duct and the flue pipe.
If the alarm “A18” appears: the stove shuts down due to the boiler

overheating. This can be caused by a lack of water circulating in the

system (pump blocked or faulty). Check that the circulation pump is

operating correctly and then cancel the alarm and restart the stove.
Only after the cause of the blockage has been permanently

eliminated can a fresh attempt to relight the stove be made.