Modbus® rtu serial communications – Precision Digital PD6400 User Manual

Page 12

Advertising
background image

Model PD6400 High Voltage & Current Meter

Instruction Manual

12

TEMPERATURE
DRIFT

0.4 µA/

°C max from 0 to 65°C ambient,

0.8 µA/

°C max from -40 to 0°C ambient

Note: Analog output drift is separate from input drift.

ISOLATED
TRANSMITTER
POWER SUPPLY

Terminals I+ & R: 24 VDC

± 10% @ 40mA. May be used to

power the 4-20 mA output or other devices. Refer to Figure
6 on page 18
and Figure 20 on page 25.

EXTERNAL LOOP
POWER SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum

Maximum

24 VDC

10

Ω

700

Ω

35 VDC (external)

100

Ω

1200

Ω

Modbus® RTU Serial Communications

SLAVE ID

1 – 247 (Meter address)

BAUD RATE

300 – 19,200 bps

TRANSMIT
TIME DELAY

Programmable between 0 and 199 ms

DATA

8 bit (1 start bit, 1 or 2 stop bits)

PARITY

Even, Odd, or None with 1 or 2 stop bits

BYTE-TO-BYTE
TIMEOUT

0.01 – 2.54 second

TURN AROUND
DELAY

Less than 2 ms (fixed)

Note: Refer to the P

RO

V

U

®

Modbus Register Tables located at www.predig.com

for details.

Advertising