VIII. Configuration for expert users



1.

Manual changes of the UPSMON.INI parameters

The UPSMON.INI configuration file includes some fields that are possible to modify by editing the file.

SYSTEM section:

[System]

OEMMode=0

1 Enables the configuration menu and the functions menu;

4 Disables the display of the Upsagent icon on the task bar;

It is possible to use a combination of these i.e. 1+2 =3.

DebugMode=0

1 Enables the view of some extended parameters in the debug mode;

3 Decodes the entire UDP packet in the TCP/IP communication;

ShutdownType=1

0 Executes only the system shutdown (computer with AT power supply);

1 Default executes system shutdown and turns off the computer power supply (ATX power supply);

In the SERIAL_00 section:

[Serial_00]

CheckRate=1

Enables the time between one request and the next for the serial communication to be incremented. This is important if there is
communications loss due to a slow computer.

2.

Console execution of Upsagent

The Upsagent service can be executed using various parameters:

¾ -debug to view all the data flow between the program and the UPS;

¾ -log to save the data flow shown in the file debug.log;

The file created can be used to solve any problems with the communication.

In Windows there are others parameters:

¾ -start to start the service;

¾ -stop to stop the service;

¾ -install to write the service in the Windows configuration registry;

¾ -remove to cancel the service from the Windows configuration registry;