Riello UPS MultiCOM 401 User Manual

Page 14

Advertising
background image

14

PZD-

PART

MultiCOM 401 is provided with a default PZD input configuration:

DEFAULT PZD INPUT CONFIGURATION

DESCRIPTION

Unit

Index

PZD1

UPS states (see the STATES table)

Flag

1

0x0001

PZD2

UPS states (see the STATES table)

Flag

2

0x0002

PZD3

Input mains voltage V1

V

12

0x000C

PZD4

Input mains voltage V2

V

13

0x000D

PZD5

Input mains voltage V3

V

14

0x000E

PZD6

Load phase L1

%

38

0x0026

PZD7

Load phase L2

%

39

0x0027

PZD8

Load phase L3

%

40

0x0028

PZD9

Remaining back-up time

Minutes

54

0x0036

PZD10 Remaining Battery Capacity

%

52

0x0034


In order to have different UPS parameters in PZD-part, the default configuration can be changed
by user as described below.

U

SER DEFINED

PZD

SLOTS

For configurations the standard parameters 915 and 916 are used to define which values are
transferred in these slots.
Parameter 915 defines output and 916 input direction. Both parameters 915 and 916 are of array
type and the subindex is used to reference the PZD slot (subindex 1 references PZD slot 1,
subindex 2 references PZD slot 2, ... subindex 10 references PZD slot 10). Parameters of type
word and byte can be selected (there is an implicit conversion byte-word). Not used PZD slots are
marked with 0 in the parameters 915 and 916.

EXAMPLES


Set input PZD3 with Input mains voltage V1 (index 12 [0x000C] UPS PARAMETER):

PKW

Word 0

Word 1

Word 2

Word 3

Output:

0x7394

0x0300

xxxx

0x000C

Input:

xxxx

xxxx

xxxx

xxxx

Word 0 → Index used 0x394 (916dec)
Word 1 → sub-index YY=03 (PZD3)
Word 3 → Value = index of Input mains voltage V1 in UPS PARAMETER table

Set input PZD10 with Battery voltage (index 48 [0x0030] UPS PARAMETER):

Word 0

Word 1

Word 2

Word 3

Output:

0x7394

0x0A00

xxxx

0x0030

Input:

xxxx

xxxx

xxxx

xxxx

Word 0 → Index used 0x394 (916dec)
Word 1 → sub-index YY=0A (PZD3)
Word 3 → Value = index of Battery voltage in UPS PARAMETER table