Thermo Pride Premiere XT 16 SEER User Manual

Page 16

Advertising
background image

16

FIGURE 17: Thermostat Wiring – Two-Stage Heat Pumps - Variable Speed Air Handler

HP 27A

Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation)

O

Reversing Valve

Energized in Cool

C

24 – Volt Common

R

24 – Volt Hot

W1 OUT

First Stage Heat

W2 OUT

Second Stage Heat

Y2 OUT

Second Stage Compressor

Y1

Single Stage Compressor

X/L

Malfunction Light

Y2

Second Stage Compressor

W

Auxiliary Heat

BS

Bonnet Sensor

BSG

Bonnet Sensor

TWO STAGE

HEAT PUMP

C

24 – Volt Common

Y1

First Stage Compressor

L

Malfunction Light

Y2

Second Stage Compressor

G

Fan

*PP32U71124
*PP32U72124

THERMOSTAT

R

24 – Volt Hot

E/W1

First Stage Aux. Heat

W2

Second Stage Aux. Heat

DHM

Dehumidistat

HM

Humidistat

Step 1 of the Thermostat

Installer Table must be

set to Heat Pump

O

Reversing Valve

Energized in Cool

1

24VAC Humidifier

(Optional)

Part Numbers:

SAP = Legacy

159481 = 031-09157

2

COM

24 – Volt Common

R

24 – Volt Hot

W1

First Stage Aux. Heat

W2

Second Stage Aux. Heat

Y1

Single Stage Compressor

Y/Y2

Second or Full

Stage Compressor

O

Reversing Valve

Energized in Cool

X/L

Malfunction Light

HUM

Dehumidification-

Open on Humidity Rise

VARIABLE SPEED

AIR HANDLER CONTROL

G

Fan

Move the MODE

jumper to “HP”

Move the HUM STAT

jumper to “YES”

if humidistat is to be used.

VARIABLE SPEED

AIR HANDLER

2

Part Numbers:

SAP = Legacy

126768 = 031-09137

18395 = 031-01996
340512 = 031-09178

1

AV

ID MODELS

SV

MV

YZE

OD MODELS

YZH

H*5

YORKGUARD VI

CONTROL

H*8

24VAC

Electronic Air Cleaner

(Optional)

E2/P Switch must be in the

E2 position

Step 2 of the Thermostat

Installer Table must be

set to 2

Step 5 of Thermostat User

Configuration Menu must

be set to “ON” for

Dehumidification

EAC(24 VAC out)

Electronic Air Cleaner

Refer to AH documentation

for W1 and W2 electric

heat staging options.

HUM OUT

(24 VAC out)

Second stage auxiliary

heat will be controlled by

the thermostat, not the

heat pump control when

wired as shown.

Change Hot Heat Pump

jumper on the heat pump

control to “ON”