Important: If you set the Assembly Instance and Size values incorrectly, the module will not
communicate over the backplane of the CompactLogix rack.
Click Next to continue.
Fill in the dialog boxes as shown, adjusting the Name, Description and Slot
options for your application. You must select the Comm Format as Data - INT in
the dialog box. Failure to set the Assembly Instance and Size values correctly
will result in a module that will not communicate over the backplane of the
CompactLogix rack. Click Next to open the next dialog box.
Select the Request Packet Interval value for scanning the I/O on the module.
This value represents the minimum frequency the module will handle scheduled
events. This value should not be set to less than 2 milliseconds.