DFCM ♦ ProLinx Gateway

DFCM Protocol Configuration

DF1 Master/Slave

Driver Manual

ProSoft Technology, Inc.

Page 33 of 88

October 15, 2010

6.2

[DF1 Port x]

The [DF1 PORT x] sections of the configuration file set the DF1 port type,

communication parameters, define the protocol specifics and set the command

list parameters. The parameters are the same for each port. Each DF1 Port also

has its own Command List.

6.2.1 Enabled

This parameter specifies if the port will be used. If the parameter is set to No, the

port is disabled. If the parameter is set to Yes, the port is enabled.

6.2.2 Type

Type : Master #M=Master, S=Slave

This parameter defines if the port will emulate a master or a slave device. Enter

Master if the port is to emulate a master device or Slave if the port is to emulate a

slave device.

6.2.3 Local Station ID

This parameter specifies the local station ID for all DF1 messages sent from this

master port. A value of 255 is not permitted as this is the broadcast address.

Enter a value in the range of 0 to 254.

6.2.4 Protocol

Protocol : Full #F=Full-Duplex, H=Half-Duplex

This parameter specifies the DF1 protocol to be used on the port. Enter Full for

full-duplex communications or Half for half-duplex communications.

6.2.5 Termination Type

Termination Type : CRC #B=BCC, C=CRC

This parameter specifies error checking for all DF1 messages. Enter CRC or

BCC.

6.2.6 Baud Rate

This is the baud rate to be used on the port. Enter the baud rate as a value. For

example, to select 19K baud, enter 19200.

6.2.7 Parity

None, Odd, Even
Parity is a simple error checking algorithm used in serial communication. This

parameter specifies the type of parity checking to use.
All devices communicating through this port must use the same parity setting.