8.7.1 Parameter Descriptions

[SECTION]/Item

Range

Description

[DF1 Master Port]

Configuration Header for DF1 Master Port

Local Station ID:

0 to 255

This parameter specifies the local station ID for all DF1
messages sent from this master port. A value of 255 will

cause the slave address to be ignored and the address

issued in the master request packet to be used as the slave

ID.

Termination Type:

BCC or

CRC

This parameter specifies the error checking for all DF1

messages. BCC or CRC

Baud Rate:

This is the baud rate to be used on the port. Enter the baud
rate as a value. For example, to select 19K baud, enter

19200.
Ports 0, 1, 2 and 3

Baud Rate

Parameter Value

110

110

150

150

300

300

600

600

1200

12 or 1200

2400

24 or 2400

4800

48 or 4800

9600

96 or 9600

14,400

14, 114 or 14400

19,200

19, 192 or 19200

28,800

28, 288 or 28800

38,400

38, 384 or 38400

Ports 1, 2 and 3 only

Baud Rate

Parameter Value

57,600

57 or 576

115,200

115 or 1152

Parity:

None,
Odd, or

Even

This is the Parity code to be used for the port. The values

are as follows: None, Odd, Even.

Data Bits:

7 or 8

This parameter sets the number of data bits for each word

used by the protocol.

Stop Bits:

1 or 2

This parameter sets the number of stop bits to be used with

each data value sent.

RTS On:

0 to

65535

This parameter sets the number of milliseconds to delay

after RTS is asserted before the data will be transmitted.

RTS Off:

0 to

65535

This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem

signal will be set low.