DFCM ♦ ProLinx Gateway

Reference

DF1 Master/Slave

Driver Manual

ProSoft Technology, Inc.

Page 53 of 88

October 15, 2010

8.3

DF1 Configuration Error Word

DF1 Configuration Error Word errors are stored in protocol-specific registers. The

following table lists the Port/Register Address configuration.

DF1 Port

Configuration Error Word Register

0

6307

1

6707

2

7107

3

7507


A register containing a code indicates a problem with the configuration. The

following table lists the codes, a description of the problem, and parameters to

correct the error condition within the configuration file.

Bit

Code

Description

0

0x0001

Invalid Enabled parameter (Yes or No)

1

0x0002

Invalid RS-Interface parameter (0 to 2)

2

0x0004

Invalid Type (Master or Slave)

3

0x0008

Invalid Protocol (RTU or ASCII)

4

0x0010

Invalid Baud Rate

5

0x0020

Invalid Parity (None, Odd, Even)

6

0x0040

Invalid Data Bits (7 or 8 bits)

7

0x0080

Invalid Stop Bits (1 or 2)

8

0x0100

Invalid Use CTS Line (Yes or No)

9

0x0200

Retry Count Invalid (0 to 10)

10

0x0400

Invalid Floating Point Data:
Float Flag not Yes or No
Float Start less than 0 or
Float Offset is Invalid

11

0x0800

Invalid Internal Slave ID (1 to 255) (Slave Only)

12

0x1000

Invalid Entry for Register Offset Data (Slave Only)

13

0x2000

Reserved

14

0x4000

Reserved

15

0x8000

Reserved