ProSoft Technology 5202-DFNT-DFCM4 User Manual
Page 53

DFCM ♦ ProLinx Gateway
Reference
DF1 Master/Slave
Driver Manual
ProSoft Technology, Inc.
Page 53 of 88
October 15, 2010
8.3
DF1 Configuration Error Word
DF1 Configuration Error Word errors are stored in protocol-specific registers. The
following table lists the Port/Register Address configuration.
DF1 Port
Configuration Error Word Register
0
6307
1
6707
2
7107
3
7507
A register containing a code indicates a problem with the configuration. The
following table lists the codes, a description of the problem, and parameters to
correct the error condition within the configuration file.
Bit
Code
Description
0
0x0001
Invalid Enabled parameter (Yes or No)
1
0x0002
Invalid RS-Interface parameter (0 to 2)
2
0x0004
Invalid Type (Master or Slave)
3
0x0008
Invalid Protocol (RTU or ASCII)
4
0x0010
Invalid Baud Rate
5
0x0020
Invalid Parity (None, Odd, Even)
6
0x0040
Invalid Data Bits (7 or 8 bits)
7
0x0080
Invalid Stop Bits (1 or 2)
8
0x0100
Invalid Use CTS Line (Yes or No)
9
0x0200
Retry Count Invalid (0 to 10)
10
0x0400
Invalid Floating Point Data:
Float Flag not Yes or No
Float Start less than 0 or
Float Offset is Invalid
11
0x0800
Invalid Internal Slave ID (1 to 255) (Slave Only)
12
0x1000
Invalid Entry for Register Offset Data (Slave Only)
13
0x2000
Reserved
14
0x4000
Reserved
15
0x8000
Reserved