Instruction Manual

IM-106-4050 Original Issue
March 2006

1-5

OxyBalance Oxygen Display

and Averaging System

SPECIFICATIONS

Specifications for the OxyBalance system are listied in Table 1-2.

Table 1-2. OxyBalance Specifications

(1)

Specifications are subject to change without notification. Our policy is one of continuous
improvement and we reserve the right to change specifications.

(2)

1.5A above 40

o

C.

SPECIFICATIONS

(1)

Ambient Environment

Temperature specification

23

o

F to 149

o

F (-5

o

C to 65

o

C)

Ambient temperature effect on electronics

Less than .01% of reading per 10

o

C

Vibration

IEC 68-2-6 and ISA S37.3

Shock

IEC 68-2-31 and ISA S37.3

Enclosure

NEMA 4X

Area Classification

General Purpose

Power Requirements

100-240 VAC, 50/60 Hz

MicroLogix 1200

Resistive Load on Current Output

0 to 500 Ohms (includes wire resistance)

Input Impedance for Current Terminal

275 Ohms

PanelView Plus 600

Minimum On-State Current

2.0 mA at 10V dc

Nominal On-State Current

8.9 mA at 24V dc

Maximum On-State Current

12. mA at 30V dc

Current per Group Common

8A

240V ac (Maximum Volts)

2.5A

(2)

(Amperes Continuous)

120V ac (Maximum Volts)

2.5A

(2)

(Amperes Continuous)

125V dc (Maximum Volts)

1.0A (Amperes Continuous)

24V dc (Maximum Volts)

2.0A (Amperes Continuous)

I/O

Signal Inputs

4-20 mA (qty. 1 to 8 O

2

probes)

Signal Outputs

4-20 mA (qty, 1 to 8 pass through each probe, qty. 4 programmable averages)

Signal Output Resolution (for averages)

12 bit

Signal Output Resistive Load

Less than 500 ohms

Discrete Inputs

"IN CAL" (qty. 2 to 8 from individual probes)

Relay Outputs

"LOSS OF PLC"
"AVERAGE WARN" if one or more probes drop out of an average.
"AVERAGE FAILED" for each average when only one probe in the average
remains valid.

Architecture

Each probe utilizes its own autonomous conditioning electronics, including its
own power supply. Any failure in the OxyBalance system will not affect the
individual 4-20 mA signals going to the control room for each probe.

Logic

4 programmable averages from 2-8 probes

Individual probes removed from average if

1.) Probe fails (4-20 mA to default condition of 3.5 mA or 21 mA
2.) Probe is in cal (SPS / IMPS contact, must share with control room)

Signal Security

4-20 mA signals to be wired in series to the PLC and to the DCS I/O marshalling
panel such that the loss of the PLC will not affect the transmission of the
individual probe signals to the DCS. If PLC power, I/O cards or processor card(s)
are lost, 4-20 mA signals from the probes are still transmitted to the control room.

Personnel Security

Password protection configuration changes in programmable averages.

Color Graphic Display

Size

6" diagonal

Type

Color Active Matrix, TFT LCD

Resolution

320 by 240 min. Touch screen operator interface