OxyBalance Oxygen Display

and Averaging System

Figure 5-6. Removal from

DIN Rail

PLC Replacement

Mounting Procedures

1. Place the top of the MicroLogix PLC over the top of the DIN rail, with the

bottom fo the PLC tilted away from the DIN rail. See Figure 5-6

2. When the top of the PLC engages the DIN rail, pivot the bottom of the

PLC in toward the DIN rail.

3. Using a screwdriver, push the DIN tabs up until they snap into position,

holding the PLC tight against the DIN rail. See Figure 5-5/

4. Attach the flat ribbon cable from the I/O modules to the PLC. See

Figure 5-4. Install the ribbon cable cover.

5. Ensure the end anchors are tight
6. Connect the wiring to the PLC that was removed in step 1 of "PLC

Removal".

7. Remove the debris shield from the PLC.

38370007

DIN Rail

Failure to remove protective debris shield before operating can cause overheating.