Initial installation, Clearances to combustibles – Enviro C-10637 User Manual

Page 11

Advertising
background image

Initial Installation

WARNING: Operation of this heater when not connected to a properly installed and maintained

venting system can result in carbon monoxide (CO) poisoning and possible death.

C

LEARANCES

TO

C

OMBUSTIBLES

:

Maintain sufficient clearances for operation, service and maintenance.

• A clearance of 25 1⁄2” (648 mm) minimum is required from the center of the unit to the sidewalls.

10" (254mm) Mantle

2" (51mm)

Mantle

39" (991 mm)

minimum to

bottom of unit

43" (1092 mm)

minimum to

bottom of unit

Figure 8: Mantle width and height.

• A 2” (51 mm) wide mantel can be mounted at a

minimum height of 39” (991 mm) from the bottom

of unit.

• A 10” (254 mm) wide mantel can be mounted at

a minimum height of 43” (1092 mm) from the

bottom of unit.

• If installed at floor level, a minimum 16” (406 mm)

non-combustible material must be installed in front

of the unit.

• If installed on a 12” (305 mm) wide hearth raised

a minimum height of 6” (152 mm), no floor

protection is required.

• Refer to Figure 9 for additional required floor

protection dimensions with different width

hearths.

Sienna

0"

(0

m

m

)

5"

(1

27

m

m

)

6"

(1

52

m

m

)

7"

(1

78

m

m

)

8"

(2

03

m

m

)

9"

(2

29

m

m

)

10

"(

25

4m

m

)

11

"(

27

9m

m

)

12

"(

30

5m

m

)

13

"(

33

0m

m

)

14

"(

35

6m

m

)

15

"(

38

1m

m

)

16

"(

40

6m

m

)

Hearth Height

of 6" (152mm)

Non-combustible

floor protection required

in front of corresponding

hearth width

6"

(1

52

m

m

)

11

"(

27

9m

m

)

12

"(

30

5m

m

)

EXAMPLE: If the Sienna is raised

6" (152mm) and has 4" (102mm)

wide hearth in front of it then 12"

(305mm) of non-combustible

floor protection is require to

be installed in front of the

hearth.

Figure 9: Floor protection distance required.

11

• If the unit is to be installed into a zero clearance fireplace the metal floor may be removed to facilitate

the installation. The stove may be installed on a combustible material if a minimum 20-gauge piece of

steel is installed under the unit. The sides and top of the structure can not be altered though baffles

and dampers can be removed.

WARNING: This fireplace cannot be used for burning wood or solid fuels unless all original parts have

been replaced and the fireplace is re-approved by the authority having jurisdiction.

Advertising