0 electrical specifications, Table 5 electrical data—50 hz systems, Lectrical – Emerson Liebert CW User Manual

Page 17: Pecifications, Table 5, Electrical data—50 hz systems, Table 6

Advertising
background image

Electrical Specifications

13

7.0

E

LECTRICAL

S

PECIFICATIONS

Table 5

Electrical data—50 Hz systems

Reheat Options

Electric

None

Electric

None

Humidifier Options

IR/SGH

IR/SGH

Steam or None

Steam or None

Models Motor HP Volts

200

230

380-415 200 230 380-415

200

230

380-415 200 230 380-415

CW026

2.0

FLA

46.7

43.4

24.3

19.8 17.2

9.9

33.9

32.3

17.9

7.0

6.1

3.5

3.0

FLA

49.8

46.1

25.9

22.9 19.9

11.5

37.0

35.0

19.5

10.1 8.8

5.1

CW038

3.0

FLA

62.9

59.0

33.2

22.9 19.9

11.5

50.1

47.9

26.8

10.1 8.8

5.1

5.0

FLA

68.6

63.9

36.0

28.6 24.8

14.3

55.8

52.8

29.6

15.8 13.7

7.9

CW041

3.0

FLA

62.9

59.0

33.2

22.9 19.9

11.5

50.1

47.9

26.8

10.1 8.8

5.1

5.0

FLA

68.6

63.9

36.0

28.6 24.8

14.3

55.8

52.8

29.6

15.8 13.7

7.9

CW051

5.0

FLA

94.6

88.4

49.6

41.2 35.9

20.7

69.2

66.2

36.8

15.8 13.7

7.9

7.5

FLA

103.9 96.5

54.2

50.5 44.0

25.3

78.5

74.3

41.4

25.1 21.8

12.5

CW060

5.0

FLA

107.9 101.4

56.8

41.2 35.9

20.7

82.5

79.2

44.0

15.8 13.7

7.9

7.5

FLA

117.2 109.5

61.4

50.5 44.0

25.3

91.8

87.3

48.6

25.1 21.8

12.5

CW076

7.5

FLA

126.6 122.6

68.6

50.5 44.0

25.3

101.2 100.4

55.8

25.1 21.8

12.5

10.0

FLA

131.7 128.4

71.2

55.6 49.8

27.9

106.3 106.2

58.4

30.2 27.6

15.1

CW084

7.5

FLA

126.6 122.6

68.6

50.5 44.0

25.3

101.2 100.4

55.8

25.1 21.8

12.5

10.0

FLA

131.7 128.4

71.2

55.6 49.8

27.9

106.3 106.2

58.4

30.2 27.6

15.1

CW106

10.0

FLA

131.7 128.4

71.2

55.6 49.8

27.9

106.3 106.2

58.4

30.2 27.6

15.1

15.0

FLA

147.1 142.4

78.9

71.0 63.8

35.6

121.7 120.2

66.1

45.6 41.6

22.8

20.0

FLA

161.5 152.8

86.1

85.4 74.2

42.8

136.1 130.6

73.3

60.0 52.0

30.0

CW114

10.0

FLA

131.7 128.4

71.2

55.6 49.8

27.9

106.3 106.2

58.4

30.2 27.6

15.1

15.0

FLA

147.1 142.4

78.9

71.0 63.8

35.6

121.7 120.2

66.1

45.6 41.6

22.8

20.0

FLA

161.5 152.8

86.1

85.4 74.2

42.8

136.1 130.6

73.3

60.0 52.0

30.0

1. FLA = FULL LOAD AMPS
2. Amperage requirements are based on the rated max FLA current of each component in the unit. The rated max FLA current of the unit is

not the sum total of all components, but is the total of the components which operate during maximum electrical load conditions.

3. The values in the table are for power demand of the unit only.
4. Units are 3-phase, 50-cycle.
5. Consult factory engineering department for electrical requirements of units with variations not listed above.

Table 6

Indoor evaporator fan motor electrical requirements—50Hz systems

Hp

Volts

200

230

380-415

2.0

FLA

7.0

6.1

3.5

3.0

FLA

10.1

8.8

5.1

5.0

FLA

15.8

13.7

7.9

7.5

FLA

25.1

21.8

12.5

10.0

FLA

30.2

27.6

15.1

15.0

FLA

46.2

42.0

24.2

20.0

FLA

NA

NA

30.0

1. Refer to General Data Section for standard fan motor size on units.
2. FLA = Full Load Amps