0 electrical data—units with ec fans, 1 cw106 and cw114 electrical data with ec fans, Table 1 electrical data—60hz-3 phase – Emerson Liebert CW User Manual

Page 9: Table 2 electrical data—50hz-3 phase, 2 cw181 electrical data with ec fans, Table 3 cw181 electrical data—60hz-3 phase, Table 4 cw181 electrical data—50hz-3 phase, Lectrical, Nits, With

Advertising
background image

Electrical Data—Units with EC Fans

5

3.0

E

LECTRICAL

D

ATA

—U

NITS

WITH

EC F

ANS

3.1

CW106 and CW114 Electrical Data with EC Fans

3.2

CW181 Electrical Data with EC Fans

Table 1

Electrical data—60Hz-3 phase

Reheat

Humidifier

Volts

FLA

WSA

OPD

Electric

Infrared

460

65.4

81.8

90

Electric

Infrared

575

53.4

66.8

70

Electric

Infrared

460

53.8

67.3

70

Electric

Infrared

575

41.8

52.3

60

None

Infrared

460

26.3

32.9

35

None

Infrared

575

23.3

29.1

30

None

None

460

14.7

15.9

20

None

None

575

11.7

12.7

15

Table 2

Electrical data—50Hz-3 phase

Reheat

Humidifier

Volts

FLA

WSA

Electric

Electric

400

70.8

88.5

Electric

None

400

58

72.5

None

Electric

400

27.5

34.4

None

None

400

14.7

15.9

Table 3

CW181 electrical data—60Hz-3 phase

Reheat

Humidifier

Volts

FLA

WSA

OPD

Electric

Infrared

460

69

86.3

90

Electric

Infrared

575

56.4

70.5

80

Electric

None

460

57.4

71.8

80

Electric

None

575

44.8

56

60

None

Infrared

460

29.9

37.4

35

None

Infrared

575

26.3

32.9

35

None

None

460

18.3

19.8

25

None

None

575

14.7

15.9

20

Table 4

CW181 electrical data—50Hz-3 phase

Reheat

Humidifier

Volts

FLA

WSA

Electric

Electric

400

74.4

93

Electric

None

400

61.6

77

None

Electric

400

31.1

38.9

None

None

400

18.3

19.8