Table 8 – Emerson Liebert CW User Manual

Page 19

Advertising
background image

Electrical Specifications

15

CW106

20.0 HP

(Upflow only)

FLA

165.1 154.8 77.7

63.7

86.0

76.2

38.6

33.6 138.5 132.6 66.1

52.1

59.4

54.0

27.0

22.0

WSA 206.4 193.5 97.1

79.6 107.5 95.3

48.3

42.0 173.1 165.8 82.6

65.1

74.3

67.5

33.8

27.5

MFCB 225

200

110

90

150

125

70

60

200

200

90

70

125

110

60

45

CW114

10.0 HP

FLA

136.5 128.8 64.7

52.7

57.4

50.2

25.6

22.6 109.9 106.6 53.1

41.1

30.8

28.0

14.0

11.0

WSA 170.6 161.0 80.9

65.9

71.8

62.8

32.0

28.3 137.4 133.3 66.4

51.4

38.5

35.0

17.5

13.8

MFCB 175

150

80

60

90

80

40

35

125

125

70

50

60

60

30

20

CW114

15.0 HP

FLA

151.9 142.8 71.7

58.7

72.8

64.2

32.6

28.6 125.3 120.6 60.1

47.1

46.2

42.0

21.0

17.0

WSA 189.9 178.5 89.6

73.4

91.0

80.3

40.8

35.8 156.6 150.8 75.1

58.9

57.8

52.5

26.3

21.3

MFCB 200

175

90

70

125

110

50

45

175

150

80

60

100

90

45

35

CW114

20.0 HP

(Upflow only)

FLA

165.1 154.8 77.7

63.7

86.0

76.2

38.6

33.6 138.5 132.6 66.1

52.1

59.4

54.0

27.0

22.0

WSA 206.4 193.5 97.1

79.6 107.5 95.3

48.3

42.0 173.1 165.8 82.6

65.1

74.3

67.5

33.8

27.5

MFCB 225

200

110

90

150

125

70

60

200

200

90

70

125

110

60

45

Table 8

Indoor evaporator fan motor electrical requirements—60Hz systems

Hp

208

230

460

575

FLA

LRA

FLA

LRA

FLA

LRA

FLA

LRA

2.0 HP

7.5

46.9

6.8

40.8

3.4

20.4

2.7

16.2

3.0 HP

10.6

66.0

9.6

58.0

4.8

26.8

3.9

23.4

5.0 HP

16.7

105.0

15.2

91.0

7.6

45.6

6.1

36.6

7.5 HP

24.2

152.0

22.0

132.0

11.0

66.0

9.0

54.0

10.0 HP

30.8

193.0

28.0

168.0

14.0

84.0

11.0

66.0

15.0 HP

46.2

290.0

42.0

252.0

21.0

126.0

17.0

102.0

20.0 HP

59.4

321.0

54.0

290.0

72.0

145.0

22.0

116.0

1. Refer to General Data Section for standard fan motor size on units.
2. FLA = FulL Load Amps

WSA = Wire Sizing Amps (Minimum supply circuit ampacity)
MFCB = Maximum Fuse or Circuit Breaker Size

3. Amperage requirements are based on the rated max FLA current of each component in the unit. The rated max FLA current of the unit

is not the sum total of all components, but is the total of the components which operate during maximum electrical load conditions.

4. The values in the chart are for power of the unit only.
5. Units are 3 phase, 60 cycle.
6. For units with other variations not listed above, consult factory engineering department for electrical requirements.

Table 7

Electrical data—60 Hz Systems (continued)

Chilled Water Models - 60Hz

Reheat Options

Electric

None

Electric

Electric

Humidifier Options

Infrared or Steam

Generating

Infrared or Steam

Generating

Steam or None

Steam or None

Models / Motor

HP

Volts 208

230

460

575

208

230

460

575

208

230

460

575

208

230

460

575