Green LED Status Codes

Green LED

Flash Code

(X + Y)

a

Indicates

Next System Action

Recommended Service Action

OFF

No “Call for Heat”

Not applicable

None

Flash Fast

Startup-Flame sense calibration

Not applicable

None

Heart Beat

Normal operation

Not applicable

None

3

Recycle

- Flame failed during run

Initiate new trial for ignition. Flash code

will remain through the ignition trial

until flame is proved.

If system fails to light on next trial for

ignition, check gas supply, pilot burner,

flame sense wiring, contamination of

flame rod, burner ground connection.

4

Flame sensed out of sequence

If situation self corrects within 10 sec-

onds, control returns to normal sequence.

If flame out of sequence remains longer

than 10 seconds, control goes to Flash

code 6 + 4 (see below).

Check for pilot flame. Replace gas valve

if pilot flame present. If no pilot flame,

cycle “Call for Heat.” If error repeats,

replace control.

7

Flame sense leakage to ground

Control remains in wait mode. When

the fault corrects, control resumes nor-

mal operation after a one minute delay.

Check flame sense lead wire for damage

or shorting. Check that flame rod is in

proper position.

Check flame rod ceramic for cracks,

damage or tracking.

8

Low secondary voltage supply -

below 15.5 Vac)

Control remains in wait mode. When

the fault corrects, control resumes nor-

mal operation after a one minute delay.

Check transformer and AC line for proper

input voltage to the control. Check with

full system load on the transformer.

6 + 2

Failed trial for ignition resulting

in lockout

Remain in lockout until “Call for Heat”

is cycled.

Check gas supply, pilot burner, spark

and flame sense wiring, flame rod con-

taminated or out of position, burner

ground connection.

6 + 3

More than 5 flame failures during

run on the same “Call for Heat”

resulting in lockout

Remain in lockout until “Call for Heat”

is cycled.

Check gas supply, pilot burner, flame

sense wiring, contamination of flame

rod, burner ground connection.

6 + 4

Flame sensed out of sequence -

longer than 10 seconds

Control waits until flame is no longer

sensed and then goes to soft lockout.

Flash code continues. Control auto re-

sets from soft lockout after one hour.

Check for pilot flame. Replace gas valve

if pilot flame present. If no pilot flame,

cycle “Call for Heat.” If error repeats,

replace control.

ON

Soft lockout due to error detected

during self check sequences

Control auto resets from soft lockout af-

ter one hour.

Reset by cycling “Call for Heat.” If er-

ror repeats, replace the control.

a

Flash Code Descriptions:

- Flash Fast: Rapid blinking

- Heartbeat: Constant 1/2 second bright 1/2 second dim cycles

- A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds,

and then repeats the sequence.

- X + Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y

times at 2Hz, remains off for three seconds, and then repeats the sequence.