Horizontal exhaust through wall installation, Installation – Enviro C-10985 User Manual

Page 11

Advertising
background image

Installation

H

ORIZONTAL

E

XHAUST

T

HROUGH

W

ALL

I

NSTALLATION

:

Vent installation: install vent at clearances specified by the vent manufacturer.

A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces,

or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired,

the installation shall conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and

Equipment. Only use venting of L or PL type with an inside diameter of 3 or 4 inches (7.6 or 10.1 cm).

1. Choose a location for your stove that meets

the requirements stated in this manual and

allows installation with the least amount of

interference to house framing, plumbing,

wiring, etc.

2. Install a non-combustible hearth pad

(where necessary).

3. Place the appliance 15” (37.5 cm) away

from the wall. If the stove is to be set on

a hearth pad, set the unit on it, and adjust

the leveling legs.

4. Locate the center of the exhaust pipe on

the stove. Extend that line to the wall.

Once you have located the center point on

the wall, refer to pellet vent manufacturer

installation instructions for correct hole size

and clearance to combustibles.

5. Install the wall thimble as per the

instructions written on the thimble. Maintain

11

Figure 11: Straight through wall Installation.

Non-combustible

floor protection.

Existing floor

(combustible)

6"

(15 cm)

4"

(10 cm)

Wall

thimble

Rodent

mesh cap

45°

elbow

12"

(30.5 cm)

Exhaust Tube

3" (75mm) or 4" (100mm) "PL" or "L" vent

Wall Thimble

45° Elbow with screen or

Termination Cap

High Temperature RTV

Silicone Required

Fresh Air Intake Tube

Figure 12: Venting to use with straight through wall Installation.

an effective vapour barrier in

accordance with local building

codes.

6. Install a length of 3” (75 mm)

or 4” (100 mm) vent pipe into

the wall thimble. The pipe

should install easily into the

thimble.

7. Connect the exhaust vent

pipe to the exhaust pipe on

the stove. Seal the connection

with

high

temperature

silicone.

8. Push the stove straight back,

leaving a minimum of 4” (10

cm) clearance from the back

of the stove to the wall. Seal

the vent pipe to the thimble

with

high

temperature

silicone.