2 xt-40 wiring diagrams, Split phase (1s101), Phase delta (high-leg) (3d101) – Eaton Electrical IM01005012E User Manual

Page 6

Advertising
background image

IM01005012E

XT-40 & IT-RSS Installation

Page 4

Rev. 1 – 2/2007

2.2 XT-40 Wiring Diagrams

Single Phase (1P101, 1P201)

CIRCUIT

INTERRUPT

DEVICE

PHASE A

GROUND

NETURAL

or PHASE B

Use Interrupt Device if

connected to Phase B

NOT Neutral

XT-40

Split Phase (1S101)

CIRCUIT

INTERRUPT

DEVICE

PHASE A

NEUTRAL

GROUND

PHASE B

Solid bond between
Ground/Earth and
Neutral at service
entrance or serving
isolation transformer

XT-40

3-Phase Wye (Star) (3Y101, 3Y201, 3Y300)

CIRCUIT

INTERRUPT

DEVICE

PHASE A

NEUTRAL

GROUND

PHASE B

PHASE C

Solid bond between
Ground/Earth and
Neutral at service
entrance or serving
isolation transformer

XT-40

3-Phase Delta (No Neut.) (NN201, NN400, NN501)

CIRCUIT

INTERRUPT

DEVICE

PHASE A

GROUND

PHASE B

PHASE C

XT-40

3-Phase Delta (High-Leg) (3D101)

XT-40

CIRCUIT

INTERRUPT

DEVICE

PHASE A

GROUND

NEUTRAL

PHASE B (High Leg)

PHASE C

Solid bond between
Ground/Earth and
Neutral at service
entrance or serving
isolation transformer