XT-40 & IT-RSS Installation

IM01005012E

Rev. 1 – 2/2007

Page 5

2.3 IT-RSS Wiring Diagram

Split Phase – 288 Vac Phase to Phase Max.

IT-RSS

CIRCUIT

INTERRUPT

DEVICE

PHASE A

GROUND

PHASE B

2.4 Installing Circuit Interrupt Devices

The SPD must be connected to the electrical system through a 30 A circuit interrupt device as listed in
Table 2-1. The circuit interrupt device can consist of fuses, individual circuit breakers (single breaker for
each phase), or a multi-pole / single throw breaker.

A pre-existing breaker of rated load size may be utilized if provisions for multi-conductor connections are
made according to U.S. NEC 110-14a (or other applicable country codes). Avoid using a pre-existing
breaker that when operated will cause a critical system shut down.

For XT-40 Single Phase applications (refer to Section 2.2, Single Phase Diagram), note that if the Neutral
wire is used as Phase B, then an additional interrupt device must be used for that phase.

Table 2-1. Wire and Circuit Interrupt Device Requirements

Circuit Interrupt Device Required

for Installation

Models

Wire Size

Max. Current Rating

Type

XT-40

IT-RSS

#10 AWG

(6 mm

2

)

Stranded Wire

Included

30 Amps

Fuse(s) or Breaker(s)

Not Included

Class RK5 Fuse(s)

or

Single-Pole / Single Throw

Breaker for each Phase

or

Multiple-Pole / Single Throw

Breaker