34-ST-03-64

Page

7

Performance Under Rated Conditions * - Model STR13D (0-5 to 0-100 psid)

Parameter

Description

Upper Range Limit **

psid

bar

100
7

Minimum Span

psid

bar

5
0.35

Turndown Ratio

20 to 1

Zero Elevation and Suppression No limit except minimum span within –18% and +100% of URL. Specifications valid from

–5% to 100% of URL.

Accuracy

(Reference – Includes

combined effects of linearity,
hysteresis, and repeatability)

• Stated accuracy does not apply

for models with 2.9 inch
diameter remote seal
diaphragms.

• Accuracy includes residual error

after averaging successive
readings.

• For F

OUNDATION

Fieldbus use

Digital Mode specifications. For
HART use Analog Mode
specifications.

In Analog Mode:

±0.1% of calibrated span or upper range value (URV), whichever is

greater, terminal based.
For URV below reference point (30 psi), accuracy equals:

±0.05 + 0.05

(

)

30 psi

span psi

or ±0.05 + 0.05

(

)

2 bar

span bar in % of span

In Digital Mode:

±0.075% of calibrated span or upper range value (URV), whichever is

greater, terminal based.
For URV below reference point (30 psi), accuracy equals:

±0.025 + 0.05

(

)

30 psi

span psi

or ±0.025 + 0.05

(

)

2 bar

span bar in % of span

Combined Zero and Span

Temperature Effect per 28°C
(50°F) ***

In Analog Mode:

±0.33% of span.

For URV below reference point (60 psi), effect equals:

±0.05 + 0.2

60 psi

span psi

⎝

⎛

⎠

⎞

or ±0.05 + 0.28

4 bar

span bar

⎝

⎛

⎠

⎞

In % span

±0.05 + 0.2

60 psi

span psi

⎝

⎛

⎝

⎛

⎠

⎞

⎠

⎞

or ±0.05 + 0.28

4 bar

span bar

⎝

⎛

⎝

⎛

⎠

⎞

⎠

⎞

In % span

In Digital Mode:

±0.305% of span.

For URV below reference point (60 psi), effect equals:

±0.025 + 0.25

60 psi

span psi

⎝

⎛

⎠

⎞

or ±0.025 + 0.28

4 bar

span bar

⎝

⎛

⎠

⎞

In % span

±0.025 + 0.25

60 psi

span psi

⎝

⎛

⎝

⎛

⎠

⎞

⎠

⎞

or ±0.025 + 0.28

4 bar

span bar

⎝

⎛

⎝

⎛

⎠

⎞

⎠

⎞

In % span

* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.

** Transmitter URL limit or maximum seal pressure rating, whichever is lower.

*** Specification applies to transmitters with 2 seals only. Apply 1.5 times factor to temperature effect for capillary lengths greater than 10
feet.