L7224 SERIES

Pressing the I button again will display the LL (Low Limit) followed

by a three-digit number and the corresponding degree designator.

See the table below for an explanation of display readout.

After approximately 60 seconds without any key presses, the

display will enter a dim display mode. To return to the bright

display mode, simply press and release any key.

Table 1. LED Error Codes

Error Code

Cause/Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCOM. wiring.

Err3

Hardware fault; replace control.

Err4

B1 fault; check B1 wiring/voltage.

Err5

Low Line; Check L1-L2, 110 Vac.

Err6

Fuse; Check ECOM wires, Replace fuse.

Err7

EEPROM, HL, LL, Hdf, Ldf, Reset to default values.

Err8

Repeated B1 fault (voltage present at B1 when

output is turned off); check B1 wiring/voltage.

Boiler Temperature

Text

Description

Display

Shows

bt

High Limit

HL

Low Limit

LL

High Limit Differential

Hdf

Low Limit Differential

Ldf

Local Thermostat Status

tt

Enviracom Thermostat Status

tte

Burner Status

brn

Circulator Status

cir

Zone Control

Zc

Zone Request

Zr

Error Code

err

Degrees Fahrenheit

f

Degrees Celsius

M22149

c

69-1957-1.fm Page 2 Tuesday, June 20, 2006 11:06 AM