Boiler is

cold,

house is

cold

Display is ON;

TT-LED is ON

B1 LED is ON

120 Vac at B1-

B2

• If no, replace control.

• If yes, check burner

and wiring

Display is ON;

TT-LED is ON

Refer to err on

display

—

Boiler is

hot, house

is cold

Display is ON;

TT-LED is ON

C1 LED is ON

120 Vac at C1-

C2

• 120 Vac at C1-C2,

check wiring to pump

• Wiring ok, is pump

running? If not,

replace the pump.

• If pump is running,

check for trapped air

or closed zone

valves.

Display is ON;

TT-LED is ON

C1 LED is OFF;
ZC LED is ON

b

Boiler below the

Low Limit

temperature,

wait for boiler to

go above Low

Limit

temperature.

Display is ON;

TT-LED is ON

ZC LED is
OFF

c

Boiler above

LL? If yes,

check for 120

Vac between ZC

and L2

• If no 120 Vac,

replace control.

• If yes, check zone

relays, circulators

and wiring.

Table 3. Troubleshooting Guide

a

.

System

Condition

Diagnostic

Condition

Check

Action

a

. Refer to Fig. 5 for Display and LED locations.

b

. ZC LED ON indicates ZC terminal power is OFF.

c

. ZC LED OFF indicates ZC terminal power is ON.