Installation – Harman Stove Company SF160 User Manual

Page 9

Advertising
background image

9

3-90-70742R11_05/13

The circulator installed between the two boilers may be hooked up to run continuously during the heating season or, an

additional s350 control (not supplied) could be installed to turn it on and off automatically. This control must be used as a

“close on rise of temperature” (jumper in cooling position).
Harman® that 1-1/4 in. pipe be used between the two boilers. also recommended is that the first section of pipe off of the

top of the Trident Boiler be threaded galvanized or threaded black-steel pipe.
The Harman® Trident Boiler is supplied with a dual function aquastat. The a350 is used to control the automatic draft control

whether open, to increase heat, or closed, to decrease heat. The s350 is used as overheat protection. since a wood or coal

fire is still producing heat when the draft is closed, this overheat protection is required. You could have the s350 energize

a circulating pump or a zone valve separate from the heating system, or it could be hooked up so that it flows the heated

water throughout the system. Either way, it must be able to flow away from the boiler.
figure 7 shows a typical schematic of the Trident boiler as a “stand alone” system. note; the crossover pipe (#12) is not

totally necessary but is recommended to provide circulation within the boiler while the heating system is satisfied. This will

ensure an even temperature within the boiler. The tempering valve shown (#10) is to prevent excessive temperature of the

domestic water.

Installation

FIG. 7

Advertising
This manual is related to the following products: