Section 3: installing the fireplace – Heat & Glo Fireplace Heat-N-Glo 6000XLT-CDN User Manual

Page 8

Advertising
background image

8

3

Installing the

Fireplace

Step 1

Locating the

Fireplace

The diagram below shows space and clearance

requirements for locating a fireplace within a room.

MODEL

A

B

C

D

E

6000TR &

42

22

37 1/8 52 1/2 74 1/4

6000XLS
6000XLT-CDN

42

22

35 1/4 49 3/4 70 3/8

6000ARCH

42*

22

35 1/4 49 3/4 70 3/8

48 1/4**

* SURROUND IN FRONT OF FINISHED WALL
** SURROUND FLUSH WITH FINISHED WALL.
NOTE: DIMENSIONS SHOWN IN INCHES.

Figure 3. Fireplace Dimensions, Locations, and

Space Requirements

Clearance Requirements

The top, back, and sides of the fireplace are defined

by stand-offs.

Minimum Clearances from the Fireplace to

Combustible Materials

Glass

Rear of

Sides of

Top of

Front

Floor

Fireplace

Fireplace

Fireplace

Ceiling

36 inches

0

1/2 inch

1/2 inch

3-1/2 inches

31 inches

(914 mm)

(13 mm)

(13 mm)

(89 mm)

(787 mm)

The minimum clearance to a perpendicular wall extend-

ing past the face of the fireplace is one inch (25 mm).
The back of the fireplace may be recessed 21 1/2

inches (546 mm) into combustible construction.