5700 act wood stove, Connection to a metal pre-fabricated chimney – Hearth and Home Technologies 820-0721 User Manual

Page 13

Advertising
background image

Page 13

September 1, 2008

5700 ACT Wood Stove

R

250-7090e

IMPORTANT!

Follow the manufacturer’s

installation instructions

and maintain the

manufacturer’s specified

clearance distances.

*

Floor

Protector

Chimney

Connector

Combustible

Ceiling

Combustible Wall

Insulated " T "

Flashing

Listed Cap

Maintain 2" (51mm)

Clearance Through eave

*

Listed

Chimney Pipe
Chimney

Connector

To Stove

Trim Collar

on Inside

Wall

Combustible Outside Wall

2" (51mm)

Clearance

Listed Chimney

Insulated " T "

Wall Support

Wall Spacer on

Outside Wall

*

refer to Clearances to Combustibles

CONNECTION TO A METAL PRE-FABRICATED CHIMNEY

When a metal prefabricated chimney is used,

the manufacturer’s installation instructions

must be followed precisely. You must also

purchase (from the same manufacturer)

and install the ceiling support package or

wall pass-through and “T” section package,

firestops (where needed), insulation shield, roof

flashing, chimney cap, etc. Maintain the proper

clearance to the structure as recommended by

the manufacturer. This clearance is usually a

minimum of 2” (51mm), although it may vary by

manufacturer or for certain components.

There are basically two methods of metal

chimney installation. One method is to install

the chimney inside the residence through the

ceiling and the roof

(Figure 13A). I

nstall an

attic insulation shield to maintain the specified

clearance to insulation. Insulation in this air

space will cause a heat buildup which may ignite

the ceiling joists.

The other method is to install

an exterior chimney that runs up the outside

of the residence

(Figure 13B). This method

of installation requires at a minimum a wall

pass-through device, a wall support package,

insulated “T” section and roof flashing. The

components illustrated may not look exactly like

the system you purchase, but they demonstrate

the basic components you will need for a

proper and safe installation.

Combustible Wall

Floor

Protector

Chimney

Connector

Ceiling Support

Listed Chimney

Maintain 2" (51mm)

Clearance

Listed Cap

Storm Collar

Flashing

*

*

*

refer to Clearances

to Combustibles

Combustible

Ceiling

Joists

Chimney

Connector

To Stove

Ceiling

Support

Specified

Clearance

Attic

Insulation

Shield

Listed

Chimney

FIGURE 13A - INTERIOR CHIMNEY

The chimney must be the required height

above the roof or other obstruction for safety

and proper draft operation. The chimney

must be a minimum of 3’ (91cm) higher than

the highest point where it passes through the

roof, and at least 2’ (61cm) higher than the

highest part of the roof or structure that is

within 10’ (305cm) of the chimney, measured

horizontally

(2-10-3 Rule Figure on page

9).

FIGURE 13B - EXTERIOR CHIMNEY

In Canada when using a factory-built chimney, make sure it is safety listed, Type UL 103 HT CLASS "A"

or conforming to CAN/ULC-S629, STANDARD FOR 650°C FACTORY-BUILT CHIMNEYS.