Commissioning

83(96)

8

- motor nominal speed
- motor nominal current

You will find the values needed for the parameters on the motor rating plate.

NOTE! You can also run the Start-up Wizard. See Chapter 7.3 or NXL HVAC quick guide for
more information.

8

Perform run test without motor

Perform either Test A or Test B:

A Controls from the I/O terminals:

a)

Turn the Start/Stop switch to ON position.

b)

Change the frequency reference (potentiometer)

c)

Check in the Monitoring menu (M1) that the value of Output frequency changes according to the
change of frequency reference.

d)

Turn the Start/Stop switch to OFF position.

B

Control from the control keypad:

a)

Change the control from the I/O terminals to the keypad as advised in Chapter 7.4.3.1.

b)

Push the Start button on the keypad

start

.

c)

Move over to the Keypad Control Menu (K3) and Keypad Reference submenu (Chapter7.4.3)
and change the frequency reference using the Browser buttons

+

-

.

d)

Check in the Monitoring menu (M1) that the value of Output frequency changes according to the
change of frequency reference.

e)

Push the Stop button on the keypad

stop

.